42
■
The assignment of the power-OFF (for compressor
and/or instantaneous heating water heater) is made
via the type of connection and by setting parameters
in the heat pump control unit.
In Germany, the power supply can be cut for a maxi-
mum of 3 x 2 hours per day (24 h).
■
The
heat pump control unit/PCB
must be supplied
without
power-OFF. Tariffs subject to possible shut-
down must not be used here.
■
When using power generated on site (use of power
generated by the PV system to meet own require-
ments):
During the power-OFF period, it is
not
possible to
operate the compressor utilising power generated on
site.
■
Protect the power cable to the heat pump control unit
with an MCB/fuse of max. 16 A.
■
For accessories and external components that will
not be connected to the heat pump control unit, pro-
vide the power supply via the same MCB/fuse, or at
least on the same phase, as the heat pump control
unit.
Connection to the same MCB/fuse provides addi-
tional safety when the power is switched off.
Observe the power consumption of the connected
consumers.
■
The PE wire of the power cable must be approx.
10 mm longer than the N and L wires.
Heat pump control unit power supply 230 V~
X3
9
16
16
F1 T6,3AH
18
N
L1
8
7
6
N
N
3
1
1
X2
X1
Fig. 38
Note
This supply must
never
be blocked.
■
Max. fuse rating 16 A
■
Standard tariff (no economy tariff with power-OFF
possible)
■
Recommended power cable: 3 x 1.5 mm
2
(5 x 1.5 mm
2
with power-OFF)
Outdoor unit power supply 230 V~/400 V~
■
Economy tariff and power-OFF can be used.
■
No parameters need to be set when using economy
tariff with power-OFF. The compressor is shut down
during the power-OFF period.
■
During power-OFF, the diagnostic functions for the
external unit are not supported.
Note
Free terminals for internal use.
Installation sequence
Power supply
(cont.)
5776 028 GB
Installation
Summary of Contents for AWT 221.A04
Page 77: ...77 Maintenance Checking the fuses cont 5776 028 GB Maintenance...
Page 87: ...87 Indoor unit parts lists Indoor unit hydraulics cont 5776 028 GB Components...
Page 90: ...90 Indoor unit parts lists Indoor unit cylinder cont 5776 028 GB Components...
Page 137: ...137 Wind direction 11 Wind loads 11 Keyword index Keyword index cont 5776 028 GB...
Page 138: ...138 5776 028 GB...
Page 139: ...139 5776 028 GB...