77
Pump/component
Parameter
Setting
For a separate cooling cir-
cuit:
"Cooling"
Ó
"Remote control, cooling
circuit 7116"
"1"
"Cooling"
Ó
"Ranking room temp.
sensor separate cooling
circuit 7106"
"0"
F16
"1"
A1/HC1
"2"
M2/HC2
"3"
M3/HC3
"4"
SKK
Vitocom 100, type GSM
"System definition"
Ó
"Vitocom 100 7017"
"1"
External extension
"System definition"
Ó
"External extension
7010"
"1"
External EA1 exten-
sion
"2"
External AM1 exten-
sion
"3"
EA1 and AM1
Note
For external function param-
eters see "External func-
tions" table.
2-stage heat pump
Parameter
Setting
Compressor 2:
■
"Enable compressor 5100"
"1"
■
"Output compressor stage 2 5130"
Value corresponding to the rated
heating output of heat pump
stage 2, see type plate
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5546 267 GB
Service