Checking the water quality
Enter the amount of top-up water, the
water hardness and the pH value in the
tables.
For water quality requirements, see
page 87.
Meter read-
ing
Fill and top-
up water
Total water
volume
Total hardness
pH value Date
Feedwater Boiler wa-
ter
m
3
m
3
m
3
mol/m
3
mol/m
3
The pH value should be between 8.2 and
9.5.
Checking the expansion vessel and system pressure
Note
Please observe expansion vessel man-
ufacturer's instructions.
Carry out this test on a cold system.
1.
Drain the system until the pressure
gauge indicates "0" or close the cap
valve on the expansion vessel and
reduce the pressure in the expansion
vessel.
Commissioning, inspection, maintenance