11
Conversion to natural gas E
Restrictor installation
BCD
EG
F
A
0
1.
Close the gas shut-off valve.
0
2.
Turn off the ON/OFF switch on the
control unit.
0
3.
Switch OFF the mains isolator (out-
side the installation room) or isolate
the mains power and secure against
unintentional reconnection.
Note
For removal of the front panels and
side panel, see from page 30
0
4.
Undo fitting
A
from the gas supply
pipe.
0
5.
Pull compensation hose
G
from
the gas train.
0
6.
Release the gas train from flange
E
.
0
7. In the case of a 500 kW burner:
Insert O-ring
B
, natural gas restric-
tor
C
and rubber cork gasket
D
.
Note
The bevel on the natural gas restric-
tor must point towards the gas
train.
In the case of a 400 and 620 kW
burner:
Remove natural gas restrictor
C
with rubber cork gasket
D
.
0
8.
Tighten screws M 5 x 16 cross-wise
(torque: 1.5 Nm).
0
9.
Secure fitting
A
.
10.
Push compensation hose
G
on to
the gas train.
11.
Affix the enclosed label "Set to ..."
over existing label
F
.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)