82
Operation: Brine/water (B0/W35)
Type BW 302.
DS090
DS110
DS140
DS180
DS230
Performance data
to EN 14511 (3 K/5 K spread)
Rated heating output
kW
84.8
108.6
137.6
174.8
222.0
Cooling capacity
kW
67.6
86.4
109.4
138.8
177.4
Power consumption
kW
18.2
23.6
29.8
37.9
47.1
Rated current of compressors (total)
A
40.3
44.9
57.0
69.9
85.6
Coefficient of performance ε (COP)
4.67
4.61
4.63
4.62
4.72
Primary circuit
(brine)
Spread
K
3
3
3
3
3
Frost protection/freezing point (rec-
ommended refrigerant Tyfocor)
°C
–
16.1
–
16.1
–
16.1
–
16.1
–
16.1
Heat exchanger capacity
l
10.5
13.1
17.4
23.0
52.4
Nominal flow rate (for sizing recom-
mended value)
m
3
/h
20.5
27.9
33.3
47.3
53.7
Minimum flow rate
m
3
/h
15.4
20.9
25.0
35.4
40.3
Pressure drop at nominal flow rate
(total pressure drop, evaporator plus
connections)
kPa
29
35
31
31
26.09
Pressure drop at minimum flow rate
kPa
16
19
17
17
15
Secondary circuit
(water)
Spread
K
5
5
5
5
5
Heat exchanger capacity
l
15.2
19.2
23.2
28.3
53.6
Nominal flow rate (for sizing recom-
mended value)
m
3
/h
14.7
19.5
23.8
32.4
38.46
Minimum flow rate
m
3
/h
11.0
14.6
17.9
24.3
28.8
Pressure drop at nominal flow rate
(total pressure drop, evaporator plus
connections)
kPa
6
7
8
10
10
Pressure drop at minimum flow rate
kPa
3
4
4
5
6
Max. flow temperature at primary in-
let B 0 °C
°C
55
55
55
55
55
Max. flow temperature at primary in-
let B +5 °C
°C
60
60
60
60
60
Note
Output data to EN 14511 corresponds to a tempera-
ture spread of 3 K at a brine inlet temperature of 0 °C
and brine outlet of
–
3 °C.
Note
A reduced flow rate results in a lower heat pump out-
put. (This also applies in partial load operation)
Note
The technical information in the datasheets and prod-
uct description describe purely physical characteristics.
Additional assurances or guarantees require a sepa-
rate contractual agreement.
Note
Parameters need to be matched in conjunction with an
ice store or the "external demand" function. Viessmann
must be consulted.
Note
The specified pressure drop refers only to the integral
heat exchangers in the heat pump and the connecting
flange.
Note
Failure to achieve the minimum frost protection may
cause damage and thus malfunction of the heat pump.
Note
Using too much antifreeze or selecting excessive frost
protection will reduce heating output.
Specification
Specification, Vitocal 300-G Pro SPS
5837251
Appendix