Victron energy SBP-100 Manual Download Page 11

4. Operation and programming

4.1. Operation modes

The Smart BatteryProtect has three operating modes, the appropriate mode can be selected via the VictronConnect app or a
programming procedure (see chapter 

Programming [10]

).

• Mode A: Buzzer or LED mode (default).

• Mode B: Relay mode.

• Mode C: Li-ion mode.

Modes A and B affect the behavior of the alarm output.

Mode C, the Li-ion mode, takes into account lithium batteries that have an external BMS or a BMS with load and/or charge
disconnect.

Buzzer or LED mode behaviour

• In case of under voltage, a continuous alarm will start after 12 seconds. The SBP will disconnect the load after 90 seconds and

the alarm will stop. Reconnect delay: 30 seconds.

• In case of over voltage, the load will be disconnected immediately and an intermittent alarm will remain on until the overvoltage

problem has been corrected. There is no reconnect delay.

Relay mode behaviour

• In case of under voltage, the relay will engage after 12 seconds. The SBP will disconnect the load after 90 seconds and the

relay will disengage.

• In case of over voltage, the load will be disconnected immediately and the alarm output will remain inactive. Overvoltage trip

levels: 16V (for a 12V system) respectively 32V (for a 24V system).

Li-ion mode behaviour

Only select the Li-Ion mode if your BMS has a load disconnect and/or a charge disconnect output. This is usually not the case
for so-called drop-in batteries with internal BMS. For lithium batteries/BMS without load disconnect output, select mode A or B
instead.

Connect the load or charge disconnect (depending on application) output of the BMS to the Remote H terminal of the Smart
BatteryProtect.

• The load or charger is disconnected 

immediately

 when the load or charge disconnect output of the BMS switches from ‘high’

to ‘free floating’. The under voltage thresholds and alarm output of the Smart BatteryProtect are inactive in this mode.

• It will remain disengaged for 30 seconds, even if it receives a re-engage signal within that time period. After 30 seconds it will

respond immediately to a re-engage signal.

Smart BatteryProtect 12/24V

Page 9

Operation and programming

Summary of Contents for SBP-100

Page 1: ...Smart BatteryProtect 12 24V 12 24V 65A 12 24V 100A 12 24V 220A rev 00 08 2022 ENGLISH...

Page 2: ...m system with external BMS and load disconnect output 7 3 3 5 Two Smart BatteryProtects for load and charger control 8 3 3 6 Smart BatteryProtect Alarm output wiring 8 4 Operation and programming 9 4...

Page 3: ...ared to the BatteryProtect the Smart BatteryProtect can be conveniently programmed via Bluetooth and our VictronConnect app or the PROG pin to GND pin method All necessary parameters can be set in thi...

Page 4: ...ooth on This is important in case of Li ion batteries especially after low cell voltage shutdown Over voltage protection To prevent damage to sensitive loads due to over voltage The load is disconnect...

Page 5: ...otection of the SBP will be activated if you try to directly connect loads with capacitors for example inverters or inverter chargers on their DC inputs For that use case please use the SBP to control...

Page 6: ...erter charger via a SBP you must use the SBP to control the inverter or inverter charger via its remote port See example below Note that the image shown below is an example for all BatteryProtect mode...

Page 7: ...the load after 90 seconds automatically DC loads Smart BatteryProtect in a simple system with wire loop between L and H input factory default The same example below This time the switch is wired betw...

Page 8: ...ly controls the SBP via its remote terminal For this the Smart BatteryProtect must be programmed to Li ion mode The dry contact is wired between the L and H connectors of the remote terminal If for ex...

Page 9: ...gh when there is an actual low cell voltage and the SBP will disconnect the load and remains off for 30 seconds even if it receives a restart signal H becomes high again within this period After this...

Page 10: ...of the SBPs always follow the current flow from IN to OUT The positive terminal of the charger goes to the IN input of the SBP DC loads SBP 65 charge SBP 65 load Two Smart BatteryProtects take contro...

Page 11: ...SBP will disconnect the load after 90 seconds and the relay will disengage In case of over voltage the load will be disconnected immediately and the alarm output will remain inactive Overvoltage trip...

Page 12: ...t to set the restart voltage 9 Click on the 3 dots in the top right corner and then on Product info 10 In the Product info menu the PIN code can be changed a custom name can be set and Bluetooth can b...

Page 13: ...0V 3 11 25V 22 5V 13 25V 26 5V 4 11 5V 23 0V 13 8V 27 6V 5 10 5V 21 0V 12 8V 25 6V 6 11 5V 23 0V 12 8V 25 6V 7 11 8V 23 6V 12 8V 25 6V 8 12 0V 24 0V 13 0V 26 0V 9 10 0V 20 0V 13 2V 26 4V User defined...

Page 14: ...f switch to the positive supply of the BMS for this purpose Similarly if a system shutdown occurred due to low cell voltage the SBP will remain disengaged for 30 seconds even if it receives a re engag...

Page 15: ...nce in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference...

Page 16: ...oad on alarm output 50mA short circuit proof Load disconnect delay 90 seconds immidiate if triggered by a BMS Load reconnect delay 30 seconds Default thresholds Disengage 10 5 V or 21 V Engage 12 V or...

Page 17: ...t draw does not exceed the SBP current rating 2 Check for loose high resistance connections and ensure that appropriate gauge wiring is used in the installation 3 Do not install the SBP unit in a loca...

Page 18: ...ween BMS and SBP Remote terminal 4 Check BMS for proper operation E8 Reverse current Reverse current protection is activated in the event that reverse current flow is detected CAUTION The SBP is desig...

Reviews: