3. Installation
3.1. What's in the box?
SmartShunt IP65
3.2. Mounting the SmartShunt
The SmartShunt has two 5.5 mm holes for mounting purposes located in the base of the SmartShunt. The holes can be used to
screw or bolt the SmartShunt onto a hard surface (screws are not included).
For the exact location of the mounting holes see the dimension drawing in the appendix of this manual.
Top view SmartShunt IP65 indicating mounting holes and side view SmartShunt indicating mounting method.
3.3. Connections overview
#
SmartShunt IP65 connection
Terminal type
A
LOAD MINUS
M10 bolt
B
BATTERY MINUS
M10 bolt
C
VE.Direct (black wire)
VE.Direct socket
D
VBatt+ (red wire with fuse)
M10 ring terminal
E
Aux (grey wire with fuse)
M10 ring terminal
3.4. Basic electrical connections
Connection procedure:
1. Connect the negative battery terminal to the M10 bolt on the "BATTERY MINUS" side of the shunt. Tighten the shunt bolt with
a maximum torque of 21Nm.
Note that there should be no other connections on this side of the shunt or on the negative battery terminal. Any loads or
chargers connected here will be excluded from the battery state of charge calculation.
2. Connect the negative of the electrical system to the M10 bolt on the "LOAD MINUS" side of the shunt. Tighten the shunt bolt
with a maximum torque of 21Nm. Make sure that the negative of all DC loads, inverters, battery chargers, solar chargers and
other charge sources are connected “after” the shunt.
3. Connect the M10 eye terminal of the red cable with the fuse to the positive terminal of the battery.
The battery monitor is now powered up. .