UG:121
Page 11
User Interface Connections
Signal Ground (CBJ3-1)
Signal Ground on CBJ3-1 is an isolated secondary ground reference for all CBJ3 interfacing signals. This
is not the same as Earth Ground on input power connector MBJ1.
Bidirectional I/O lines (CBJ3-4 to CBJ3-9)
(Enable/Disable or Module Power Good Status)
Enable/Disable Mode
Enable/Disable mode is the default condition for these I/O lines. In this mode, the control pins allow
the outputs to be sequenced either ON or OFF. To disable a module, the E/D pin should be pulled low
to less than 0.7V with respect to signal ground. The E/D lines will typically source 250mA (1mA max.)
under this condition. To enable a module, a E/D pin should be open circuited or driven high to a
logic-high voltage of 3.5V (40mA typical) or greater not to exceed 5V. (When one has a two module
array, use GSD to disable the output instead of using E/D.)
The correspondence between a module and its E/D line as seen from the output end of the power
supply goes from left to right. The PFC Micro™ power supply is a two-slot box. Slot 1 is the left slot and
Slot 2 is the right slot. See Table 1. E/D1, E/D2, E/D3 correspond with VOUT M1, VOUT M2 and VOUT
M3 on slot 1. E/D4, E/D5, E/D6 correspond with VOUT M1, VOUT M2 and VOUT M3 on slot 2.
Module Power Good Status Mode
The power supply will enter the Power Good status mode when logic high (50mA typical) is applied to
Power Good Read (PGR) pin (CBJ3-2). After transitioning to PGR mode the I/O lines (CBJ3-4 to CBJ3-9)
will be outputs and will give a onetime readout of the associated module status. These outputs give an
indication of the status of the modules of the power supply at the time of transition to PGR. A TTL "1"
(>3.5V) on a line indicates the module is ON and functioning properly and a TTL "0" (<0.7V) indicates
the module is either OFF or is not functioning properly. The correspondence between the module and
the Power Good status of that module is the same as between a E/D pin and its module. This mode
does NOT constantly monitor the module status and must be re-triggered by transitioning the PGR pin
from logic-low to logic-high to get current module status.
Procedurally, certain guidelines must be followed when using this feature. Upon application of a
logic-high on the Power Good Read (PGR) pin, the user must change its E/D interface (CBJ3-4 to
CBJ3-9) from outputs to inputs within 3ms. The Power Good status data will be valid on the E/D lines
when the Power Good Data Valid (PGDV) pin (CBJ3-11) asserts to a logic-high. The Power Good status
measurement takes typically 200ms. While in the Power Good Read mode (PGR=1) the individual
shut-down lines are not functional. However, General Shut Down (GSD) is functional. Leaving the Power
Good Read mode is accomplished by removing the logic-high or applying a logic-low (<0.7V) to the
Power Good Read (PGR) pin (CBJ3-2). The user must change its E/D interface (CBJ3-4 to CBJ3-9) from
inputs to outputs between 1 and 4ms of the time the PGR-low is applied to pin CBJ3-2.
Note:
If any model is disabled by the user when a Power Good Read is requested (PGR=1), that module will remain
off during the Power Good Read and status of said module will be power not good (<0.7V). Power Good Read status
data on open E/D lines are not valid. An open E/D line is a E/D pin where there is no module associated with said E/D
line (i.e., A power supply with two Maxi modules, data on E/D2, E/D3 and E/D5 and E/D6 are NOT valid.
The Power Good Status mode feature is only valid when Maxi, Mini and/or Micro modules are used.
The following page shows examples of triggering PGR with a 1Hz square while monitoring PGDV and a
selected E/D line with a good module and a defective one.
Table 1
Enable/Disable mode
Module
Slot 1
Slot 2
E/D1
E/D2
E/D3
E/D4
E/D5
E/D6
Maxi
X
X
Mini
X
X
X
X
Micro
X
X
X
X
X
X
VI-200™
X
X
VI-J00™
X
X
X
X