UG:107
Page 2
Standard Features
n
n
Input: 3-phase 208 / 240V
AC
Wye or Delta, 1-phase 180 – 264 (47 – 500Hz) or 260 – 352V
DC
n
n
Power Output: 3-Phase MegaPAC™: 2,000W with 3-phase input;
1,200W with 1-phase input; 1 – 20 outputs
4kW MegaPAC™:
4,000W with 3-phase input;
1,500W with 1-phase input; 1 – 20 outputs
n
n
Ten slots (up to 20 outputs)
n
n
Fan cooled (the 4kW MegaPAC has two fans)
n
n
Full-power to 45°C; half power to 65°C
n
n
Power factor correction (passive) 0.92PF (3-phase input)
n
n
Conducted EMI meets EN 55022 Level A
n
n
AC Power OK and AC Power Fail status signals
n
n
Output Sequencing and General Shut Down
(Consult Applications Engineering for automatic sequencing circuitry)
n
n
Autosense (Refer to pages 13 and 17 for more information on Autosense)
n
n
Overcurrent protection on all outputs
n
n
Overtemperature limiting (not applicable with VI-J00™ modules)
n
n
Output overvoltage protection (not applicable with VI-J00 modules)
n
n
Ride-through time: >20ms at nominal line (full load)
n
n
Size: 4kW MegaPAC: 4.9 x 7.5 x 14in [124,5 x 190,5 x 355,6mm] Regular chassis
Size: 3-Phase MegaPAC: 4.9 x 7.5 x 12.3in [124,5 x 190,5 x 312,4mm] Regular chassis
n
n
Safety Agency Approvals: CE Mark, UL, CSA, TÜV
Optional Features
n
n
DC OK status signal
n
n
Output voltage adjustment range with built-in potentiometer
n
n
Reversed fan air-flow direction
n
n
Industrial-grade screening of output converters
n
n
Current Share Boards (see pages 26 – 28)
Mechanical Considerations
The 3-Phase MegaPAC and 4kW MegaPAC can be mounted on any of four surfaces using standard
8-32 or 4mm screws. The chassis comes with four mounting points on each surface; maximum
allowable torque is 20lb.in. The maximum penetration is 0.15in [3,8mm].
When selecting a mounting location and orientation, the unit should be positioned so air flow is not
restricted. Maintain a two inch minimum clearance at both ends of the 3-Phase MegaPAC and 4kW
MegaPAC and route all cables so air flow is not obstructed. The standard unit draws air in at the
fan side / AC input side and exhausts air out the load side. If air-flow ducting is used, use caution, as
sharp turns could present back pressure to the 3-Phase MegaPAC and 4kW MegaPAC. The fans move
approximately 50CFM of air for the 4kW MegaPAC and 30CFM for the 3-Phase MegaPAC. The 4kW
MegaPAC has a second fan for additional cooling capabilities.
Avoid excessive bending of output power cables after they are connected to the 4kW MegaPAC or
3-Phase MegaPAC. For high-current outputs, use cable ties to support heavy cables in order to minimize
mechanical stress on output studs. Be careful not to short-out to neighboring output studs. The
3-Phase MegaPAC and 4kW MegaPAC is supplied with serrated, flanged hex-nuts on all output studs,
so thread-locking compounds or lock washers are not required. The maximum torque recommended
on flanged nuts is 45lb.in. Never loosen the inner nut on a ConverterPAC™. This nut supports the
hardware inside the ConverterPAC and is factory torqued.
Avoid applications in which the unit is exposed to excessive shock or vibration levels. In such
applications, a shock-absorption mounting design is required.