background image

1

R820 SERIES

SCR POWER CONTROLS

 

240 Vac up to 600 Vac models

 

10 Amps up to 75 Amps models

 

1 phase or 3 phase models

DESCRIPTION                                                                       

The Viconics R820 series SCR power controls are designed
for cost effective, precise modulation of electric loads for
most electric heating applications.

Applicable on resistive loads only

 )

The R820

 series consists of SCR’s power controls, c/w

factory assembled heatsink for surface or in-panel mounting.

FEATURES                                                                            

 Microcomputer 

based.

 Dip 

switch 

configurable

 

Integrated over temperature thermostatic protection (self
resetting) Auto shut off when SCR ambient temperature
is above 82°C ( 180°F )

 

Complete with factory installed heatsink

 

For surface or in-panel mounting

 

CSA

 approved for Canada and USA

 

UL

 recognized

 

Pulse status led for servicing & trouble shooting

 

2 years warranty

They are compatible with many industry standard signals. A
typical application would be to control a modulating electric
duct heater with a 0 to 10 Vdc control signal from an analog
room thermostat. The R820 power controller also contain
four dip switch to adjust to the following control signals:

  0 to 10 Vdc control signal   ( 2 to 10 Vdc control range )

  4 to 20 mA control signal

  0 to 135 

 control signal

SCR INSTALLATION                                                             
Important.
All external safety devices like: contactors, relays, flow
switch & thermal protections are to be supplied and
installed by other.
When the SCR is installed inside a panel, the enclosure
needs to be adequately louvered for proper ventilation
and heat dissipation. Call the factory for the derating
amperage curves for these specific applications.
Electronic controls require special care for wiring and
startup. To avoid problems, carefully follow the
procedures below.

Look at the wiring diagrams, and study them carefully. Be
sure that you understand how the system is supposed to
work.
A)

Location:

1- Can be installed inside a louvered approved cabinet

or with the heatsink mounted externally.

2- Must be installed away from excessive heat source.
3- Nothing must restrain air circulation to the heatsink.

B)

Installation:

1-  If installed completely inside a cabinet, use the

mounting tabs on the heatsink to secure the SCR to
the back plate of the panel.

2-  If installed with heatsink outside the cabinet, use the

proper model mounting template for the cut out
dimensions and to check for mounting obstructions.

3-  Respect mounting orientation

( this side up ).

4-  Mount the heatsink vertically on the side of the

cabinet for proper heat dissipation.

5-  Do not relocate the power switching modules on the

heatsink.

HOW TO ORDER                                                                                                                                                                       

Models Available

Maximum Voltage

Maximum Amperage

Phase

R820-211

Up to 240 V.

10 A.

1 Phase

R820-213

Up to 240 V.

10 A.

3 Phase

R820-321

Up to 347 V.

25 A.

1 Phase

R820-323

Up to 347 V.

25 A.

3 Phase

R820-341

Up to 347 V.

45 A.

1 Phase

R820-343

Up to 347 V.

45 A.

3 Phase

R820-421

Up to 480 V.

25 A.

1 Phase

R820-423

Up to 480 V.

25 A.

3 Phase

R820-441

Up to 480 V.

45 A.

1 Phase

R820-443

Up to 480 V.

45 A.

3 Phase

R820-471

Up to 480 V.

75 A.

1 Phase

R820-621

Up to 600 V.

25 A.

1 Phase

R820-623

Up to 600 V.

25 A.

3 Phase

R820-641

Up to 600 V.

45 A.

1 Phase

R820-643

Up to 600 V.

45 A.

3 Phase

R820-671

Up to 600 V.

75 A.

1 Phase

**

 

 

Only 2 legs of the circuit are controlled on 3 phase systems

.