8) Indicates a channel name assigned by the user in the ZOOM Configuration software. The description may
contain up to 32 characters, however only the first 28 characters are displayed.
9) Indicates the input parameter type associated with this sensor.
10) Indicates processing selected for the sensor, if any.
11) Indicates the configured trending and alarm range.
12) Alarm levels (single threshold, or lower and upper thresholds) set for this input channel.
3.3.1 View spectral band parameters
The CIM-4/20, ICPM-1.13, FIM-40-100, ICPM-5.65-500, and FIM-40-100(LF) acquisition modules can be
programmed with spectral analysis firmware designed for monitoring specific frequencies and protecting fixed
components on large rotating units. These modules perform high speed acquisition for advanced analysis as
well as alarm surveillance on either a broadband frequency range or specific, user-selected spectral bands.
Pressing ENTER on a channel will display the sensor’s spectral band parameters.
Important Information
•
Spectral band values are only displayed if the vibration option has been selected in the module
configuration window of the ZOOM Configuration software. A firmware is then automatically installed on
the module.
1) Displays broadband values for a given sensor.
2) Displays spectral band values for a given sensor. Represents amplitude in correlation with frequency. Up
to 5 different spectral bands can be observed.
3) The information that appears in this section reflects which band has been highlighted with the cursor:
broadband or spectral band. This window is also available if the parameter is not configured for spectral
band surveillance, however, only broadband values will be displayed.
32
ZPU-5000 Acquisition and Processing Unit with ZOOM Version 7.4 - User’s Manual