VESDA-E VES-A00-P Product Guide
www.xtralis.com
3
1
Introduction
The VESDA-E VES-A00-P is a scanning aspirating smoke detector (ASD) that provides very early warning of
fire conditions by drawing air samples through an air sampling pipe network. The VESDA-E VES-A00-P can
monitor and individually report on four sectors in the protected area.
Figure 1-1: VESDA-E VES-A00-P Scanning Aspirating Smoke Detector
The detector easily interfaces with fire warning and fire suppression release systems, and can be integrated
into a building management system (BMS).
1.1
Features
The VES-A00-P detector contains the following features:
l
Sector addressability for up to four sectors or zones
l
Adaptive scan threshold
l
Short wavelength laser-based detection
l
Inherent absolute calibration
l
Clean air barrier for optics protection
l
More robust contamination resistance
l
Four configurable alarm levels per sector and a wide sensitivity range
l
Flow fault thresholds configurable per port
l
Long-life, easy-to-replace air sample filter
l
Quiet operation
l
Advanced remote diagnostics
l
Area coverage: up to 2,000 m² (21,520 ft²) (VES-A00-P)
l
Up to four inlet pipes
l
Total maximum pipe length: Four pipe VES-A00-P: 560 m (1,837ft)
l
Referencing
l
AutoLearn™ Smoke and Flow
l
12 programmable relays
l
Two General Purpose Inputs (GPIs), one monitored and one unmonitored
l
Ultrasonic flow sensing
l
Xtralis VSC, Xtralis VSM4 and ASPIRE PC software support
l
IP 40 enclosure (not UL tested)
l
Easy mounting with steel support bracket
l
Field replaceable aspirator, sampling module, filter, detection chamber, ultrasonic flow sensing and
scanner module
l
VESDAnet networking
l
Ethernet 100 base T
l
WiFi, 802.11 b/g/n
l
Local host mode USB port
l
Easy cable termination access
l
Event Log (20,000 events)
Summary of Contents for VESDA-E VES-A00-P
Page 2: ......
Page 10: ...VESDA E VES A00 P Product Guide 4 www xtralis com This page is intentionally left blank ...
Page 20: ...VESDA E VES A00 P Product Guide 14 www xtralis com This page is intentionally left blank ...
Page 50: ...VESDA E VES A00 P Product Guide 44 www xtralis com This page is intentionally left blank ...
Page 80: ...VESDA E VES A00 P Product Guide 74 www xtralis com This page is intentionally left blank ...
Page 84: ...VESDA E VES A00 P Product Guide 78 www xtralis com This page is intentionally left blank ...
Page 101: ...VESDA E VES A00 P Product Guide www xtralis com 95 Figure 7 21 Undo Sampling Module screws ...
Page 106: ...VESDA E VES A00 P Product Guide 100 www xtralis com ...
Page 108: ...VESDA E VES A00 P Product Guide 102 www xtralis com This page is intentionally left blank ...
Page 110: ...VESDA E VES A00 P Product Guide 104 www xtralis com This page is intentionally left blank ...
Page 112: ...VESDA E VES A00 P Product Guide 106 www xtralis com This page is intentionally left blank ...
Page 118: ...VESDA E VES A00 P Product Guide 112 www xtralis com This page is intentionally left blank ...
Page 124: ...VESDA E VES A00 P Product Guide 118 www xtralis com Z zone 55 56 79 113 ...