Specifications A
VES, LLC
Elite-RS Panel Installation Manual
VF3529-00, Revision E01.03
H-Series
64 of 146
This appendix provides electrical and environmental specifications for the Elite-RS Panel.
Electrical
The electrical specifications provided for Standby and Alarm Current are typical values.
Standby and Alarm Current
Earth Fault Indication
A ground fault indication occurs on the Elite-RS Panel when a minimum of 30K Ohms exists between earth-ground
and either DC RTN or +24 VDC of the power-supply.
SLC Ratings
Loops
Standby
Alarm (mA)
Description
1
160 mA @ 120 VAC
220 mA @ 120 VAC
Line current for standby and alarm when
battery current is less than 30 mA.
200 mA @ 24 VDC
220 mA @ 24 VDC
Battery current for standby and alarm when a
power failure condition occurs on the AC line.
2
200 mA @ 120 VAC
250 mA @ 120 VAC
Line current for standby and alarm when
battery current is less than 30 mA.
270 mA @ 24 VDC
290 mA @ 24 VDC
Battery current for standby and alarm when a
power failure condition occurs on the AC line.
Terminal
Connection
Rating
19
Loop 1 (+ IN)
32 VDC @ 250 mA
20
Loop 1 (- IN)
21
Loop 1 (+ OUT)
32 VDC @ 250 mA
22
Loop 1 (- OUT)
38
Loop 2 (+ OUT)
32 VDC @ 250 mA
39
Loop 2 (- OUT)
40
Loop 2 (+ IN)
32 VDC @ 250 mA
41
Loop 2 (- IN)
Appendix A
Specifications