Installation 3
VES, LLC
Elite-RS Panel Installation Manual
VF3529-00, Revision E01.03
H-Series
38 of 146
3
Press 3 on the upper-control-pad to display the MAIN MENU.
MAIN MENU – V07.0007H
>DISABLEMENTS
VIEW DeviceS
TEST ZONES
SET SYSTEM TIME
SENSOR MAINTENANCE EARLY WARNING
ACCESS LEVEL 3
4
Press 3 on the upper-control-pad to navigate down to TEST ZONES.
MAIN MENU – V07.0007H
DISABLEMENTS
VIEW DeviceS
>TEST ZONES
SET SYSTEM TIME
SENSOR MAINTENANCE EARLY WARNING
ACCESS LEVEL 3
5
Press 2 on the upper-control-pad to select TEST ZONES.
TEST ZONES MENU
>TEST ZONE: 01 – (NORMAL)
Use Up/Down arrow keys to select.
Press > to proceed. Press < to go back.
6
Press 1 on the upper-control-pad to select a TEST ZONE from 1 to 500.
7
Press 2 on the upper-control-pad to select the TEST ZONE option for LOCAL NAC: - ON.
TEST ZONE: 1
>LOCAL NAC: - ON
Use Up/Down arrow keys to select.
Press > to proceed. Press < to go back.
8
Press 1 on the upper-control-pad to set LOCAL NAC: - OFF.