![VES Elite-RS H-Series Installation Manual Download Page 27](http://html1.mh-extra.com/html/ves/elite-rs-h-series/elite-rs-h-series_installation-manual_1008675027.webp)
Installation 3
VES, LLC
Elite-RS Panel Installation Manual
VF3529-00, Revision E01.03
H-Series
17 of 146
Before You Begin
Before you begin the installation, take a few minutes to review the installation information, gather the required items,
and complete the tasks listed below to make the installation as quick and easy as possible.
Determining System Current Draw
Determine the current draw of the fire alarm system for alarm and standby conditions. Use these maximum current
values to obtain the battery capacity of the fire alarm system as well as to confirm the operating constraints of the
system.
Standby-Battery Capacity
Perform the installation only after calculations have been completed for a suitable battery size.
Battery standby-hours are dependant on battery capacity and load of the FACP system.
Reference Appendix C, Calculations to determine the standby-battery capacity of the system.
1
Create a plan and checklist before beginning the installation process. Planning can reduce the
number of problems that can occur during installation.
2
Select a mounting site for the Elite-RS Panel that is suitable for its operating environment. The site chosen
for mounting the Elite-RS Panel should be clean and dry and not subject to shock or vibration. Ensure that
the Elite-RS Panel environment is free from wire ends, knockout discs and any other debris.
3
Acquire the following items that are not included with the Elite-RS Panel, but may be required for the
installation:
Item
Quantity
Description
Dual phone
Cable
1
The dual phone cable connects to an RJ31X jack assigned to line 1 and to
an RJ31X jack assigned to line 2.
Reference Figure 3-16, Integrated Dialer Connections for more
information on dual phone cable wiring.
Mounting
Hardware
1
The mounting hardware that secures the Elite-RS Panel to the
premises-wall is not provided in the Elite-RS Panel packaging.
Ground Strap
1
A ground strap is required for handling Elite-RS Panel circuit boards.
The ground strap is not provided in packaging of the Elite-RS Panel.
CAUTION!
The Elite-RS Panel installation must be performed by qualified personnel familiar with electronic
components. Electronic components within the Elite-RS Panel are vulnerable to damage from electrostatic
discharge. Ground straps must be worn by installers before handling Elite-RS Panel circuit boards to prevent
damage from electrostatic discharge.
CAUTION!
Disconnect power before removing Elite-RS Panel circuit boards. Never insert or remove circuit boards while
the Elite-RS Panel power is on. The Elite-RS Panel can be damaged if its circuit boards are removed while
under power.