Lower-Control-Pad
The figure below illustrates the lower-control-pad:
Figure 2-5
Lower-Control-Pad
Alarm
Silence
Panel Sounder
Silence
Lam p
Test
Reset
Fire Drill
Program m able
Function
Enable Access
Re-Sound
Alarm
B
C
D
E
F
G
A
H
Key
Name
Description
A
Re-Sound Alarm
Re-sounds the alarm when sounders are silenced using the Alarm Silence
button.
B
Alarm Silence
Silences NACs connected to the Elite-RS Panel after receiving authorization
through Access Level 2.
C
Panel Sounder
Silence
Mutes the internal buzzer of the Elite-RS Panel. No other sounder outputs are
effected by this operation.
D
Lamp Test
Tests front-panel indicators and the internal buzzer by illuminating all LEDs while
darkening the front-panel display and sounding the buzzer.
E
Reset
Resets latching inputs such as fire and pre-alarm events after receiving
authorization through Access Level 2. Fault events are non-latching inputs and
cannot be cleared by the Reset button. Non-latching inputs are cleared when
faults are cleared.
F
Fire Drill
Provides a fire drill for the Elite-RS Panel after receiving authorization through
Access Level 2. During the drill:
•
The “On Test” LED illuminates continuously
•
The “Fire” LED blinks
•
The internal buzzer sounds intermittently
•
The display provides the message,
“FIRE DRILL:FIRE DRILL ZONE 00*
To stop the fire drill:
1 Press 4 to display the “SET ACCESS LEVEL 2 MENU”.
2 Provide Access Level 2 authorization.
3 Press Reset or Fire Drill on the lower-control-pad.
G
Programmable
Function
Activates inputs, outputs or actions defined in the configuration by the installer.
H
Enable Access
This feature places the menu of the Elite-RS in ACCESS LEVEL 2. Insert the
key in the lock and turn it to the right to obtain ACCESS LEVEL 2.