Communications Format F
VES, LLC
Elite-RS Panel Installation Manual
VF3529-00, Revision E01.03
H-Series
108 of 146
After try 5, a communications failure is declared. This failure will restore once a transmission is successful.
The user will note that another ten tries will occur after this sequence. These additional tries would be indicative of
attempts to send the comm. failure event.
Answering Methodology
The embedded dialer allows incoming calls to line #1 only. The Incoming methodology allows users to remotely pro-
gram through Loop Explorer configuration software. Additionally VES technical support can use this facility to assist
with diagnostics of the system.
24 Hour Test Report
The embedded dialer will send a 24 hour test report signal based upon the test code time filled in within the Accounts
tab of the configure dialer settings dialog. If the 4
th
reporting criteria (Report Service/Test) box is not enabled, no test
signal will be generated.
Configure Dialer Settings
Loop Explorer [VES PC Panel programming Software] allows the user to configure the embedded dialer based upon
the elements of a particular installation and the monitoring center being used. Although the dialer may be configured
through level 3 setting at the front of the panel, not all options are panel programmable, and ease of operation is much
more favorable with Loop Explorer.
After an auto-learn, a RS panel even though equipped with a dialer, will not provide any dialer functionality without
user programming. Once an auto-learn has been accomplished, connect a programming cable to your laptop and the
computer port of the control panel. Make certain the slide switch on the control panel is set to PC and not dialer.
Perform synchronization from the panel to your computer.
Once complete a screen similar to Figure F-1 will be present:
Figure F-1
Completed Screen