Vertiv Intelligent Rack PDU
Page 60
f.
Type in the desired
Clear Delay
time in seconds. Any value other than "0" means once this Event
is tripped, the measurement must return to normal for this many seconds before the Event will clear
and reset. Clear Delay can be up to 14400 seconds (4 hours).
g.
Type in the desired
Trip Delay
time in seconds. Any value other than "0" means that the measure-
ment must exceed the threshold for this many seconds before the Event will be tripped. Trip Delay
can be up to 14400 seconds (4 hours).
h.
Latching Mode
: If enabled, this Event and its associated Actions (see below) remain active until
the Event is acknowledged, even if the measurement subsequently returns to normal.
i.
To determine where the alert notifications will be sent to when this particular Alarm or Warning
Event occurs, click the Add icon to create a new Action, then select the desired options from the
drop-down menu:
Figure 3-21 Add Page
•
Target
is the email address or SNMP manager to which notifications should be sent when the Event is
tripped.
NOTE
Note: Target Delays and Repeats are shared across all alarms. If multiple
Delay and/or Repeat values are needed for specific Targets, each one must
be added to the Target list and then the appropriate ‘Enabled’ box checked
on each alarm. See screen-shot below for example.