Vertiv Intelligent Rack PDU
Page 59
•
: Delete Existing Alarms & Warnings.
3.
Notification: Notify user of tripped Events, and request acknowledgment.
•
Empty: No alert condition.
•
: Acknowledge button. When a Warning or Alarm Event has occurred; the user can click on this
symbol to acknowledge the Event and stop the unit from sending any more notifications about it.
Note: Clicking this symbol does not clear the Warning or Alarm Event, it just stops the notifications
from repeating.
4.
The actual conditions for the various Alarms & Warnings settings are shown here.
5.2.1.2.1. ADD/MODIFY ALARMS & WARNINGS
To add a new Alarm or Warning Event:
1.
Click the Add/Modify Alarms & Warnings button:
Figure 3-20 Adding Alarms and Warnings
2.
Set the desired conditions for this Event as follows:
a.
Select the
Name
of the phase or circuit you wish to set an Event on.
b.
Select the measurement (current, voltage, etc.) you want to
Trigger
the Event.
c.
Set the
Severity
level ("Warning", or "Alarm") for this Event.
d.
Select the threshold
Type
, "high" (trips if the measurement goes above the threshold) or "low" (trips
if the measurement goes below the threshold).
e.
Type in the desired
Threshold Value
(any number between -999.0 ~ 999.0 is valid).