Table 14:
Rectifier Indicators
Indicator
Normal State Alarm State
Alarm Cause
Power
(Green)
On
Off
No input voltage.
Internal input fuse open.
Flashing
The rectifier is being identified by the
controller.
Protection
(Yellow)
Off
On
AC input under/over voltage.
PFC output under/over voltage.
Moderate load sharing imbalance.
Rectifier not inserted into the slot
completely.
Rectifier over-temperature protection.
Rectifier in ECO Standby Mode when ECO
Mode is active in controller.
Flashing
Loss of communication with the controller
(the rectifier can provide power).
Alarm
(Red)
Off
On
Severe load sharing imbalance.
Rectifier output disabled for any reason,
including overvoltage shutdown and
internal output fuse open.
Rectifier addresses contradictory.
Flashing
Fan not operating (rectifier module shuts
down).
Installing Rectifiers
The rectifier is hot swappable. It can be installed with the system operating.
WARNING!
To prevent damage to the latching mechanism, ensure the handle is in the open position
when installing or removing a rectifier. NEVER hold the handle in the closed position when installing a
rectifier into a shelf.
Procedure
NOTE!
as this procedure is performed.
1.
Unpack the rectifier.
2.
Place the rectifier into an unoccupied mounting slot without sliding it in completely.
3.
Loosen the captive fastener securing the top of the latch mechanism to the front of the rectifier. Pull
the top of the latch mechanism away from the rectifier (this will retract the latch mechanism located on
the underside of the rectifier). Refer to
for latch mechanism illustration.
4.