Vertiv™ NetSure™ External Distribution Box (EDB) Description and Installation Manual
Proprietary and Confidential © 2022 Vertiv Group Corp.
33
Figure 11.10 -48 VDC / -58 VDC Input Power Connections
12
Sealing Enclosure Cable Entries
In keeping with best industry practices, seal all cable grommets against weather, rodent and insect intrusions.
It is extremely important to maintain a well-sealed enclosure. Failure to do so can jeopardize the equipment housed in the enclosure.
All cable interfaces into the enclosure must be properly sealed after installation of cables.
Procedure
1.
Seal all cable entries with duct putty after passing cables through the cable grommets.
-48 VDC / -58 VDC Input Connections
3/8-16 Studs on 1” Centers
(Customer must supply additional hardware)
Maximum Lug Width: 1.06 inches.
Torque (3/8” Hardware using
Standard Lock Washer): 300 in-lbs.
Torque (3/8” Hardware using
Belleville Lock Washer): 180 in-lbs.
Front doors remove in
illustration for clarity only.
Front
-48 VDC / -58 VDC Input
Left Side Distribution Panel
-48 VDC / -58 VDC Input
Right Side Distribution Panel
Return Lead
-48 VDC / -58 VDC
Input Lead
-48 VDC / -58 VDC
Input Lead
Return Lead