3.2.4
Typical Input Data: 60 Hz input.
(A)
System output is initially adjusted to 54.48 volts DC as measured at the output bus at 50% of full load and
nominal input.
Number
of Rectifiers
Installed
Nominal
Input
Voltage
Percent
of Full
Load
Input Current
(Amperes)
Input
VA
Input
Watts
Power
Factor
Efficiency
%
1
480
0
1.35
1122
0
0.074
--
25
3.78
3147
2713
0.908
94.0
50
6.99
5813
5429
0.973
95.9
75
10.30
8563
8120
0.987
96.1
100
13.66
11358
10797
0.992
95.9
(B)
Typical Efficiency versus Output Current:
(C)
Maximum input current at 100% of full load with output adjusted to 58 volts DC as measured at the output bus.
Nominal
Input
Voltage
Input
Voltage
Number of
Rectifiers
Installed
Input Current
(Amperes)
480
408
1
17.5
2
35.0
3
52.5
4
70.0
5
87.5
6
105.0
7
122.5
8
140.0
9
157.5
10
175.0
3.3
Input Ratings (208VAC, with 486534003 rectifier)
3.3.1
Voltage: Nominal 208 volts AC, three phase, 60 Hz, with an operating range of 176 to 264 volts. Acceptable input
frequency range is 47 to 63 Hz.
3.3.2
Harmonic Content: Complies with IEEE-519-1992. Voltage harmonic distortion of less than 5% when operating on a
line impedance of 0.104 ohms or less.
3.3.3
Inrush Current: Peak does not exceed 6 times the RMS input current at full load, under any conditions of input
voltage within the rated input voltage range stated in Paragraph 3.2.1 and for any duration of AC input interrupts.
Under the above conditions, standard AC distribution circuit breakers will not trip.