-48 VDC Power System
System Application Guide
Spec. No: 582140001
Proprietary and Confidential © 2022 Vertiv Group Corp.
SAG582140001
Model No: 801
NLDB
, 801
NLEB
, 801
NL
-
B
Page 48
Revision T, September 28, 2022
Distribution Bay Frame Grounding Wire Sizes and Lugs Selection
Features
♦
1/4” clearance holes on 5/8" centers are provided for installation of customer provided two-hole lugs, as shown in the
following illustration.
Restrictions
All lugs for customer connections must be ordered separately.
Customer needs to supply lug mounting bolts and hardware
.
The recommended frame grounding wire size is 6 AWG.
Recommended lug P/N 245346700.
Top View
Distribution Bay
1/4" clearance holes
on 5/8" centers are
provided for installation
of customer provided
two-hole lug.
1/4" clearance holes
on 5/8" centers are
provided for installation
of customer provided
two-hole lug.