Vertiv
|
NetSure -48V DC Bulk Output Power System Installation and User Instructions (UM582127100)
|
Rev. E
42
Figure 14:
-48V DC Output Connections
GND RTN
Busbars
-48V DC
Output
Busbars
GND RTN
Busbars
-48V DC
Output
Busbars
GND RTN
Busbars
-48V DC
Output
Busbars
GND RTN
Busbars
-48V DC
Output
Busbars
GND RTN
Busbars
-48V DC
Output
Busbars
Rear
Rear
Rear
Rear
Rear
1-Shelf System
2-Shelf System
3-Shelf System
(1) connection per
two shelves.
(1) connection per
two shelves (top).
(1) connection per
two shelves (bottom).
(1) connection per
two shelves (top).
(1) connection per
single shelf (bottom).
(1) connection per
two shelves (top).
(1) connection per
two shelves (middle).
(1) connection per
single shelf (bottom).
(1) connection per
single shelf.
4-Shelf System
5-Shelf System
-48V DC OUTPUT CONNECTIONS
3/8 Clearance Holes on 1” Centers
(Customer must order or supply
ug mounting hardware.)
Maximum Lug Width:
1.31” for three (3) lugs per polarity.
1.78” for two (2) lugs per polarity.
DC Output Connection Options
1. Route cables left, right, or out the back
by repositioning the lug landing busbars.
2. Make connections to each shelf
(List 10 and 11).
3. Make connections to every
two (2) shelves (List 20 and 21).