48
Installing Optional Lug Adapter Busbar Kits, Part Nos. 534449 and 514714
These kits provide lug adapter busbars plus hardware for use with 2-pole and 3-pole bullet circuit breakers.
Contents of Kit P/N 534449 (for 2-pole circuit breakers)
Qty. Part No.
Description
1
534447
Busbar
1
534448
Busbar
8
214110100
Flat Washer, 1/4”
4
214112100
Flat Washer, 3/8”
8
215111100
Lock Washer, 1/4”
4
215111300
Lock Washer, 3/8”
4
227640400 Hex Head Bolt, 1/4-20 x 3/4”
(not used)
2
227646600 Hex Head Bolt, 3/8-16 x 1”
8
228557100 Nut, 1/4-20
2
228567100 Nut, 3/8-16
Contents of Kit P/N 514714 (for 3-pole circuit breakers)
Qty. Part No.
Description
1
514676
Busbar
1
514678
Busbar
12 214110100
Flat Washer, 1/4”
4
214112100
Flat Washer, 3/8”
12 215111100
Lock Washer, 1/4”
4
215111300
Lock Washer, 3/8”
6
227640400 Hex Head Bolt, 1/4-20 x 3/4”
(not used)
2
227646600 Hex Head Bolt, 3/8-16 x 1”
12 228557100 Nut, 1/4-20
2
228567100 Nut, 3/8-16
Perform the following steps to install the lug adapter busbars.
Procedure
as the procedure is performed. Note also the restrictions on location in
1.
Open the distribution cabinet’s front door by turning the latch in the counterclockwise position
(system’s in a relay rack), or open the system’s enclosure door.
2.
Install the lug adapter busbars as shown in
. Apply anti-oxidizing compound to busbar mating
surfaces before assembling. Recommended torque is 72 in-lbs using the supplied 1/4” bolts and
hardware.
3.
Orient the load lug hardware as shown in
. Recommended torque is 300 in-lbs using the
supplied 3/8” bolts and hardware.
4.
Close the distribution cabinet’s front door and turn the latch clockwise to secure the door (system’s in a