INSTALLING THE RECTIFIER AND
DC-DC CONVERTER MODULES
The module location diagram on the front of each shelf shows which type modules can be operated in that
shelf. (See
.) Rectifiers will operate in any mounting position in any shelf. If a shelf accepts DC-DC
converter modules, they must be installed in any or all of the four middle mounting positions.
NOTE!
Each rectifier and DC-DC converter module locks into the module mounting assembly by means
of a latch located on the right-hand side of the module. The latch and module handle are interactive.
Pushing the handle into the module front panel causes the latch to extend to the locking position;
pulling the handle out from the module front panel causes the latch to retract. See
operation.
WARNING!
To prevent damage to the latching mechanism, ensure the handle is in the open position
when installing or removing a module. NEVER hold the handle in the closed position when installing a
module into a shelf.
Procedure
1.
Unpack the modules.
2.
Note the model number located on the handle of each module. Model numbers starting with the letter
“R” (R24-2500 or 24-3000) are rectifiers. Model numbers starting with the letter “C” (C24/48-1500) are
DC-DC converter modules.
3.
Check the module location diagram on the front of the shelf to determine which type of module (rectifier
or DC-DC converter) can be installed in each mounting position. See
4.
If present, remove blank cover panels from the mounting positions into which rectifier or DC-DC
converter modules are to be installed.
5.
Place the module into an unoccupied mounting slot without sliding it in completely.
6.
Loosen the captive screw on the module handle. Pull the handle to pivot it out of the module front panel
(this will also retract the latch mechanism located at the right side of the module). See
7.
Push the module completely into the shelf.
8.
Push the handle into the front panel of the module. This will lock the module securely to the shelf.
Tighten the captive screw on the handle.
9.
Repeat the above steps for each module being installed in the system.
10.
After the modules are physically installed in the mounting shelf(s), they are ready for operation