2.5 Connecting Power to Liqui-tect
WARNING! Liqui-tect LP6000 requires a dedicated circuit breaker that is clearly marked as the
disconnection device for the [[[Undefined variable Liquitect.ModelNo]]] controller. Make sure
that the dedicated circuit break is off before connecting the AC power wires to the
[[[Undefined variable Liquitect.ModelNo]]] controller. Follow all state and local codes.
1. Engage a certified electrician to run an isolated power supply to the location of the unit.
2. Remove knockouts, as necessary, from the bottom of the unit, then route the power supply into
the enclosure to the power-input terminal block, and insert the wires a shown on the back
plate: Neutral - Line - Ground, see
3. Before applying power to the unit, make sure that all connections are correct and all screw
terminals are secure.
4. Apply power and wait approximately 1 minute for the LP6000 to start up.
There may be alarms because the leak-detection cable is not yet connected.
5. Verify that power is connected, and verify that the leak-detection cable is working by touching
it with a clean, moist cloth or paper towel.
If the cable is properly connected, an audible alarm sounds and an alarm notification displays
on the digital display.
NOTE: Do not saturate the leak-detection cable for testing. A small amount of water triggers an alarm,
and the cable must dry for the alarm to clear.
6. Dry the cable to remove the alarm condition. Use a hair dryer to speed up drying if needed.
7. Once you verify that the leak-detection cable is working, you are ready to calibrate the cable,
map leak-detection points and test the installation. See
Mapping and Testing the Installation
2.6 Calibrating Resistance to Cable Length
The leak-detection cable has a base resistance of 4 ohms/ft. Because of manufacturing variances, the
base resistance of each length of leak-detection cable may be slightly more or less than 4 ohms/ft, which
means that the displayed length may be slightly more or less than the actual length of the cable.
While a configuration using base resistance values is very accurate, you can fine-tune the resistance to
make it more precise to increase accuracy and bring the reported cable-length value in line with the
actual cable length.
To calibrate cable resistance:
1. Make sure that the LP6000 controller is powered-on, has all sensing cables attached, and that
there are no alarms.
2. Record the following data from the home page of the web UI:
DATA
RECORDED INFO
Cable length reported by LP6000.
Cable current
Leg 1 resistance
Leg 2 resistance
Vertiv
| Liqui-tect LP6000 Installer/User Guide |
15
Summary of Contents for Liqui-tect LP6000
Page 1: ...Liqui tect LP6000 Leak detection System Leak detection System Installer User Guide...
Page 18: ...Vertiv Liqui tect LP6000 Installer User Guide 18 This page intentionally left blank...
Page 20: ...Vertiv Liqui tect LP6000 Installer User Guide 20 This page intentionally left blank...
Page 34: ...Vertiv Liqui tect LP6000 Installer User Guide 34 This page intentionally left blank...
Page 60: ...Vertiv Liqui tect LP6000 Installer User Guide 60 This page intentionally left blank...
Page 74: ...Vertiv Liqui tect LP6000 Installer User Guide 74 This page intentionally left blank...
Page 76: ...Vertiv Liqui tect LP6000 Installer User Guide 76 This page intentionally left blank...
Page 80: ...Vertiv Liqui tect LP6000 Installer User Guide 80 This page intentionally left blank...
Page 81: ......