4 SPECIFICATIONS
Battery Cabinet Parameters
Values
Top-Terminal Cabinet
Front-Terminal Cabinet
Battery Type
VRLA (Valve Regulated Lead-Acid)
Nominal Battery Bus, VDC
480V
Battery Float Voltage, VDC
540V
Minimum EOD Voltage, VDC
384V (for VRLA / Flooded Lead-Acid)
Physical Parameters and Standards
Width, in. (mm)
1
Standard Width: 56.5 (1435)
Reduced Width: 48.3 (1227)
63.0 (1600)
Depth, in. (mm)
2
33.5 (850)
33.5 (850)
Height, in. (mm)
76.8 (1950)
76.8 (1950)
Weight, lb (kg) approx.
Standard Color
Black (ZP-7021)
Front Door Opening (for serviceability)
More than 180°
Degree of Protection for UPS Enclosure
IP 20 (with and without front door open)
Minimum Clearance, Top
24" (610mm)
Minimum Clearance, Back
0 in.
Minimum Clearance, Sides
0 in.
Cable Entrance
Top or Bottom
Standards and Conformities
UL 1778; CSA 22.2 107.3
FCC Part 15, Class A; ISTA Procedure 1H; WEEE;
IBC 2012/CBC 2010
Environmental Parameters
Storage Temperature Range
-4°F to 104°F (-20°C to 40°C)
3
74°F to 80°F (23-27°C) for optimal battery life
Table 4.1 Liebert Battery Cabinet Specifications
4 Specifications
29
Summary of Contents for Liebert
Page 1: ...Liebert Large UPS Battery System Installer User Guide ...
Page 4: ...Vertiv Liebert Large UPS Battery System Installer Guide ii This page intentionally left blank ...
Page 6: ...Vertiv Liebert Large UPS Battery System Installer Guide 2 This page intentionally left blank ...
Page 14: ...Vertiv Liebert Large UPS Battery System Installer Guide 10 This page intentionally left blank ...
Page 39: ...Vertiv Liebert Large UPS Battery System Installer Guide ...