4.6 Removing Units from the Pallet
WARNING! Risk of unsecured unit rolling off of pallet. Can cause equipment damage, injury, or death. The
unit is on casters. Ensure that the unit and pallet are located on a flat surface before loosening the hardware
securing the unit to its shipping pallet.
CAUTION: Risk of contact with sharp edges, splinters, and exposed fasteners. Can cause injury. Only
properly trained and qualified personnel wearing appropriate, OSHA approved PPE should attempt to move,
lift, remove packaging from, or prepare the unit for installation.
NOTICE
Risk of overhead interference. Can cause unit and structure damage. Unit may be too tall to fit through a
doorway while on or off pallet. Measure unit and doorway heights and refer to installation plans prior to moving
unit for clearance verification.
NOTICE
Risk of unit damage if improperly stored. Keep unit vertically upright, indoors, and protected from dampness,
freezing temperatures, and contact damage.
IMPORTANT! Two or more properly trained and qualified personnel are required to move the unit to its installation
location.
1.
Open the top panel door with mounted control. See
•
Using a 5/16-inch hex head or slotted screwdriver, remove the screws securing the bottom front panel
assembly, and set aside until instructed to re-attach.
•
Close and latch the top panel door.
4 Equipment Inspection and Handling
19
Summary of Contents for Liebert XDU 060
Page 1: ...Liebert XDU Liquid to Air Heat Exchanger for Chip Cooling Installer User Guide 600 mm Wide ...
Page 10: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 6 This page intentionally left blank ...
Page 38: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 34 ...
Page 74: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling ...