Components
Number of Units or Piping Length, feet
Pounds Per Component
Total, lb.
Liebert XDP/Liebert XDC
1
157
157
Liebert XDV8 Cooling Modules
20
2.32
46.4
Supply Main, 1-1/8"
100
0.45
45
Return Main, 2-1/8"
100
0.28
28
Liebert XDV 1/2" supply Liebert XD Flex Pipes
20
0.8
16
Liebert XDV 5/8" return Liebert XD Flex Pipes
20
0.03
0.6
Total
293
Table 3.18 Calculating refrigerant charge—example
Components
Number of Units or Piping Length
Pounds Per Component
Total
Total
Table 3.19 Worksheet to calculate refrigerant charge
Verify that the refrigerant volume of the Liebert XD system with the longest piping length is within the
allowable limit. If the allowable limit is exceeded, the Liebert XDP/Liebert XDC should be moved closer to
the cooling modules (refer to
on page 55 for limits and related details). Another
way to shorten the total pipe length is to reroute the pipe runs.
3.24 Chilled Water Piping
The Liebert XDP is offered only with a two-way chilled water control valve. Some applications may require
the use of a pressure activated bypass valve to prevent dead-heading of the chilled water pump. This
bypass valve must be specified by the engineer responsible for design of the chilled water field piping
system.
NOTICE
Risk of particles in chilled water. Can cause equipment damage and reduced cooling.
Failure to install a strainer in the supply line to the Liebert XDP can result in damage to the unit’s heat
exchanger.
Install a 20-40 mesh strainer on the chilled water supply to the Liebert XDP. The strainer is required to
prevent particles in the chilled water from entering the heat exchanger of the Liebert XDP. The maximum
distance of the strainer from the Liebert XDP is 10 feet (3m).
Vertiv
| Liebert® Xtreme Density™ System Design Manual |
58
Summary of Contents for Liebert XD Series
Page 1: ...Liebert Xtreme Density System Design Manual...
Page 18: ...Vertiv Liebert Xtreme Density System Design Manual 18 This page intentionally left blank...
Page 20: ...Vertiv Liebert Xtreme Density System Design Manual 20 This page intentionally left blank...
Page 66: ...Figure 4 2 Overall dimensions Vertiv Liebert Xtreme Density System Design Manual 66...
Page 88: ...Figure 4 21 Liebert XDV dimensions Vertiv Liebert Xtreme Density System Design Manual 88...
Page 152: ...Vertiv Liebert Xtreme Density System Design Manual 152 This page intentionally left blank...
Page 166: ...Figure 7 7 Modules on a single chain Vertiv Liebert Xtreme Density System Design Manual 166...
Page 167: ...Figure 7 8 Modules on two chains Vertiv Liebert Xtreme Density System Design Manual 167...
Page 182: ...Vertiv Liebert Xtreme Density System Design Manual 182 This page intentionally left blank...
Page 199: ......