Figure 3.24 Efficient piping layout—avoid “bull head T” connections
3.20 Piping Installation Method Prefabricated Headers
The assembly and connection means used for piping in the Liebert XD system are similar to those used
for conventional refrigeration systems. All piping should be installed with high-temperature brazed joints.
Soft solder is not recommended. During brazing, the lines must be filled with flowing dry nitrogen to
prevent excessive oxidation and scale formation inside the piping. Prevailing good refrigeration practices
must be employed for piping supports, leak testing, dehydration and charging. Failure to use good system
practices may result in damage to the system. Refer to the ASHRAE refrigeration handbook for general
good-practice refrigeration piping.
Follow all guidelines in
Liebert XD Piping System Design
on page 38 and
page 40 during installation.
Vertiv
| Liebert® Xtreme Density™ System Design Manual |
47
Summary of Contents for Liebert XD Series
Page 1: ...Liebert Xtreme Density System Design Manual...
Page 18: ...Vertiv Liebert Xtreme Density System Design Manual 18 This page intentionally left blank...
Page 20: ...Vertiv Liebert Xtreme Density System Design Manual 20 This page intentionally left blank...
Page 66: ...Figure 4 2 Overall dimensions Vertiv Liebert Xtreme Density System Design Manual 66...
Page 88: ...Figure 4 21 Liebert XDV dimensions Vertiv Liebert Xtreme Density System Design Manual 88...
Page 152: ...Vertiv Liebert Xtreme Density System Design Manual 152 This page intentionally left blank...
Page 166: ...Figure 7 7 Modules on a single chain Vertiv Liebert Xtreme Density System Design Manual 166...
Page 167: ...Figure 7 8 Modules on two chains Vertiv Liebert Xtreme Density System Design Manual 167...
Page 182: ...Vertiv Liebert Xtreme Density System Design Manual 182 This page intentionally left blank...
Page 199: ......