8 MONITORING
The Liebert XDC and Liebert XDP with iCOM allow for control down to the Smart Module level. Many of the
Liebert XD system data points can be monitored through a building management system. For specific
protocol mapping, refer to the protocol specific reference guide for registers, available at
www.VertivCo.com.
Data Description
Definitions
Auto Restart Delay
If power is lost, the control will delay this amount of time after power is restored before restarting the unit.
Calculated Next
Maintenance Month
Calculated month of the next scheduled maintenance. Used in conjunction with (Calculated Next Maintenance Year).
Calculated Next
Maintenance Year
Calculated year of the next scheduled maintenance. Used in conjunction with (Calculated Next Maintenance Month).
Circuit 1 Low Suction
Pressure
Compressor Circuit 1 low suction pressure.
Circuit 2 Low Suction
Pressure
Compressor Circuit 2 low suction pressure.
Compressor 1A High
Head Pressure
Compressor 1A High Head Pressure
Compressor 1A Short
Cycle
Compressor 1A short cycle. A short cycle is defined as turning On and Off a number of times over a set time period.
Compressor 1A State
Compressor 1A operational state.
Compressor 1B High
Head Pressure
Compressor 1B high head pressure.
Compressor 1B Short
Cycle
Compressor 1B short cycle. A short cycle is defined as turning On and Off a number of times over a set time period.
Compressor 1B State
Compressor 1B operational state.
Compressor 2A High
Head Pressure
Compressor 2A high head pressure.
Compressor 2A Short
Cycle
Compressor 2A short cycle. A short cycle is defined as turning On and Off a number of times over a set time period.
Compressor 2A State
Compressor 2A operational state.
Compressor 2B High
Head Pressure
Compressor 2B high head pressure.
Compressor 2B Short
Cycle
Compressor 2B short cycle. A short cycle is defined as turning On and Off a number of times over a set time period.
Compressor 2B State
Compressor 2B operational state.
Customer Input 1
Customer Input 1.
Dew Point Temperature
Dew point temperature, using the highest reading from all sensors.
Ext Air Over Temp
Threshold
Threshold value used in the ([Ext Air Sensor A Over Temperature], [Ext Air Sensor B Over Temperature]...) events.
Ext Air Sensor A Dew
Point Temp
Dew point temperature as measured by External Air Sensor A.
Ext Air Sensor A
Humidity
Relative humidity as measured by External Air Sensor A.
Ext Air Sensor A Issue
The External Air Sensor A is disconnected or the signal is out of range.
Ext Air Sensor A Over
Temperature
(Ext Air Sensor A Temperature) has exceeded (Ext Air Over Temp Threshold).
Table 8.1 Liebert XDC/XDP monitoring points
Vertiv
| Liebert® Xtreme Density™ System Design Manual |
177
Summary of Contents for Liebert XD Series
Page 1: ...Liebert Xtreme Density System Design Manual...
Page 18: ...Vertiv Liebert Xtreme Density System Design Manual 18 This page intentionally left blank...
Page 20: ...Vertiv Liebert Xtreme Density System Design Manual 20 This page intentionally left blank...
Page 66: ...Figure 4 2 Overall dimensions Vertiv Liebert Xtreme Density System Design Manual 66...
Page 88: ...Figure 4 21 Liebert XDV dimensions Vertiv Liebert Xtreme Density System Design Manual 88...
Page 152: ...Vertiv Liebert Xtreme Density System Design Manual 152 This page intentionally left blank...
Page 166: ...Figure 7 7 Modules on a single chain Vertiv Liebert Xtreme Density System Design Manual 166...
Page 167: ...Figure 7 8 Modules on two chains Vertiv Liebert Xtreme Density System Design Manual 167...
Page 182: ...Vertiv Liebert Xtreme Density System Design Manual 182 This page intentionally left blank...
Page 199: ......