Installation Drawings
Vertiv
|
Large System, 3-Phase UPS Battery System Installation Manual
41
Figure 39
Terminal details, Liebert NXL
™
500kVA UPS to top-terminal battery and attached junction cabinet, point-to-point
wiring
Table 7
Terminal details, Liebert NXL 500kVA UPS to top-terminal battery and attached junction cabinet, point-to-point
interconnect wiring
Run
From
To
Conductors
A1
Battery Cabinet Negative Bus
Junction Negative Bus
Negative DC Power (LH Mount)
B1
Battery Cabinet Positive Bus
Junction Positive Bus
Positive DC Power (LH Mount)
A2
Battery Cabinet Negative Bus
Junction Negative Bus
Negative DC Power (RH Mount)
B2
Battery Cabinet Positive Bus
Junction Positive Bus
Positive DC Power (RH Mount)
D
Junction Positive Bus
UPS Cabinet Positive Bus
Positive DC Power
E
Junction Negative Bus
UPS Cabinet Negative Bus
Negative DC Power
F
Junction Ground
UPS Cabinet Ground
Ground
G
Battery Cabinet
Battery Interface Board (BIB)
UPS External Interface Board (EIB)
CAN Control Cables
TOP VIEW
Attached Junction
B A
E
D
F
UPS Left Side
UPS Left Front (Part A)
Ground
Bus
DC Input
C
B
A
DC (+)
Input
DC (-)
Input
Cabinet Right Side
Rectifier (Part A)
C
A1 and B1
LH Mount
A1
B1
A2 and B2
RH Mount
A2
B2
Battery Cabinet
G
C
C
G
D
E
Summary of Contents for Liebert NXL 1100
Page 2: ...Liebert Large System 3 Phase UPS Battery System Installation Manual...
Page 69: ...Specifications Vertiv Large System 3 Phase UPS Battery System Installation Manual 62 NOTES...
Page 70: ...Specifications Vertiv Large System 3 Phase UPS Battery System Installation Manual 63...
Page 71: ...Specifications Vertiv Large System 3 Phase UPS Battery System Installation Manual 64...