6 TEAMWORK, STANDBY AND ROTATION FOR COOLING UNITS
NOTE: Your Liebert® DSE™ Packaged Solution does not offer humidification or dehumidification functions. Please
disregard those settings/fields when mentioned in this guide or displayed on the iCOM controller.
iCOM unit to unit communication via private network and additional hardware allows the following operating features for the
cooling units. (See
•
Teamwork
•
Standby (Rotation)
•
Cascade
6.1 Continuous Control with Virtual Master
The Virtual Master function maintains smooth control if group communication is compromised. In these operating
configurations, a lead (master) unit is in charge of component staging in teamwork mode, unit staging, and stand-by
rotation. If the lead unit gets disconnected, iCOM automatically assigns a virtual master, which assumes the responsibilities
of the lead unit until communication is restored.
6.2 Teamwork Modes
When iCOM controlled thermal management units are connected to a network in a group or team, use teamwork to
optimize performance and efficiency depending on the mode chose and its application.
In a panel with Status content, the Teamwork mode icon indicates the mode selected, Figure 6.1 on the next page.
Touching the icon displays the Teamwork dialog from which you can access the teamwork control settings.
6.2.1 To Set Up Team Work
1.
Touch the Teamwork-mode icon, then touch
Edit
on the teamwork dialog.
– or –
Touch
, then
>
BMS & Teamwork Setup
>
Teamwork / Standby
>
TeamworkMode
.
2.
Select the mode from the
Teamwork Mode
drop down in the TEAMWORK MODE CONTROL panel. The
TEAMWORK/STANDBY panel opens.
3.
Touch
Save
. Teamwork mode is set.
•
Touch
Cancel
to discard changes.
6 Teamwork, Standby and Rotation for Cooling Units
63
Summary of Contents for Liebert iCOM DP400/500
Page 8: ...Vertiv Liebert iCOM Installer User Guide vi This page intentionally left blank...
Page 64: ...Vertiv Liebert iCOM Installer User Guide 56 This page intentionally left blank...
Page 70: ...Vertiv Liebert iCOM Installer User Guide 62 This page intentionally left blank...
Page 86: ...Vertiv Liebert iCOM Installer User Guide 78 This page intentionally left blank...
Page 90: ...Vertiv Liebert iCOM Installer User Guide 82 This page intentionally left blank...
Page 110: ...Vertiv Liebert iCOM Installer User Guide 102 This page intentionally left blank...
Page 140: ...Vertiv Liebert iCOM Installer User Guide 132 This page intentionally left blank...
Page 178: ...Vertiv Liebert iCOM Installer User Guide 170 This page intentionally left blank...