Figure 7.1 Replacing the Battery Pack
6.2 Charging Batteries
The batteries are LiFePO4 type Lithium-ion batteries. They should be kept charged to maintain their design life. The Vertiv™
Liebert® GXT5 Lithium-Ion charges the batteries continuously when it is connected to input power. If the UPS will be stored
for a long time, Vertiv recommends connecting the UPS to input power every 4 to 6 months for at least 3 hours to ensure
recharge of the batteries.
The Lithium-ion batteries used in the Liebert® GXT5 Lithium-Ion series, as well as all Vertiv Lithium-Ion UPSs, contain a
Battery Management System (BMS) that self-monitors the safety of the Lithium-ion batteries in real time. This is an agency
tested and certified requirement now eliminating the industry wide safety risk known with previous Lithium-ion batteries.
6.3 Checking UPS Operation
NOTE: Operation check procedures may interrupt output power supplied to the connected load.
We recommend checking the UPS operation once every 6 months. Ensure that output power loss to the connected load will
not cause data loss or other errors before conducting the check.
1.
Press the
Enter
button to check the indicators and display function.
2.
Check for alarm or fault indicators on the operation/display panel.