3.3.1 Cooling
The recommended maximum return-air temperature is 105°F (40°C) and maximum dew point is 59°F
(15°C). The recommended minimum return-air temperature setpoint Dry Bulb is 85°F (29°C).
Operating outside this envelope can decrease equipment reliability.
NOTE: If running in supply-air control, the minimum supply-air setpoint is 68°F (20°C), and the
maximum supply air temperature is 80°F (27°C).
NOTE: When running above 77°F (25°C) supply air temperature, the superheat readings on the
refrigeration circuits may be higher than 7.2°F (–14°C). The EEVs will run out of stroke and limit mass
flow, which will result in higher than normal superheat.
3.4 Unit Weights
Model
Weight, lb (kg)
DP060 Perimeter
5,500 (2,495)
Table 3.3 DP060 unit weights