Figure 3.2 Correct and Incorrect condensate-drain line
Item
Description
1
Correct drain-line installation
2
Incorrect drain-line installation
3
DSE unit
4
Internal drain
5
External drain
6
Continuous downward slope
7
External trap. Do not trap externally.
8
External traps, although unintentional. Lines must be rigid enough not to bow over top of other objects.
Table 3.2 Evaporator Drain-line Figure Descriptions
3.3 Operating Conditions
The Liebert® DP060 must supply air to a conditioned space within the operating envelope that ASHRAE
recommends for data centers. Operating the DP060 outside of this envelope can decrease equipment
reliability. Refer to ASHRAE’s publication, “Thermal Guidelines for Data Processing Environments.”
Vertiv | Liebert® DSE060™ Installer/User Guide
16