43
Vertiv I Liebert ITA2 30kVA I Manual
3.6.4
Connecting LBS Cables
1. The appearance of the LBS port is the same as the parallel port (see Figure 1-3).
2. For the dual bus system formed by the parallel UPS, it is recommended to prepare
two LBS cables used to connect any two parallel/LBS ports of the two parallel
system, which is used for reliable connection.
Figure 3-9
LBS cable connection
3.6.5
Setting Parameters Of LBS
The LBS parameters setting interface is shown in Figure 3-10.
Procedures for setting LBS parameters:
Through the 'Settings' -> 'System' -> 'LBS', you can set the LBS according to actual needs.
There are three items of LBS for selection: Disable, Slave, Master.
Monitor
System
LBS select
IT system compatibility
Dry connect 1 (Input)
Disable
Maintain...
Low battery
Disable
Dry connect 2 (Output)
Figure 3-10 LBS parameters setting interface
UPS1
UPS2