Vertiv I Liebert ITA2 30kVA I Manual
2.7.2
Start-up Interface
If the system is first start-up, only mains input mode can be used, and the LCD screen will
display the start-up interface, see Figure 2-1
7
.
Start Up Guidance(1/5)
Next
Thanks for using Vertiv UPS!
Press Enter to start
Figure 2-17 Start-up interface
2.7.3
Normal Mode Start-Up
1. Close the external output MCB and input MCB of the UPS one by one. If the single POD is
selected to connect with the UPS, close the input MCB, bypass MCB and output MCB of the
POD.
After closing the UPS extenal output MCB or the POD output MCB, the output
terminal block of the UPS, output terminal block of the POD and power distribution
end of the load will be live, pay attention to personnal safety to avoid electric shock.
Note whether it is safe to feed power to the load.
2. The rectifier runs in normal state for about 30 seconds, the start-up of the rectifier is
finished.
3. Finish and check the parameter settings of the single UPS.
a) At main menu screen, press the
or
key to select 'Settings', and press the
key
to enter the interface shown in Figure 2-1
8
.
Status
Settings
Control
Log
About
Maintain
Figure 2-18 Main menu screen