Installation Drawings
Vertiv
| Liebert
®
EXM
™
Parallel Cabinet User Manual |
22
Figure 10 Outline drawing—800mm Liebert EXM Parallel Cabinet
EXM12016
Rev. 2
Front View
Right Side View
Bottom View
Top View
DETAIL A
Leveler
Caster
39.8" (1010mm)
28.3" (719mm)
31.8" (808mm)
31.3" (800mm)
78.7"
(2000mm)
34.3"
(872mm)
1.8"
(45mm)
See DETAIL A
28.3"
(719mm)
Breakout
Centers
22.8"
(579mm)
Control Cable Entry
4.7" x 1.6" (119mm x 41mm)
Power Cable Entry
26.8" (681mm) X 16.8" (427mm)
Power Cable Plate
28.3" (719mm) X
17.5" (445mm)
Control Cable Entry
5.9" x 2.0"
(150mm x 51mm)
2.9" (74mm)
NOTES:
1. All dimensions are in inches (mm).
2. 24" (610) minimum clearance above unit for air exhaust.
36" (914) front access required for service.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry is available through removable access
plates. Remove, punch to suit conduit size and replace.
5. Unit bottom is structurally adequate for forklift handling.
6. Control wiring and power wiring must be run in separate conduits.
7. All wiring is to be done in accordances with national and local
electrical codes.