Chapter 11 Specifications 137
Liebert EXM 80kVA ~ 200kVA UPS User Manual
Chapter 11
Specifications
This chapter lists the UPS specifications.
11.1
Conformance And Standards
The UPS has been designed to comply with the European and international standards listed in Table 11-1.
Table 11-1
European and international standards
Item
Normative reference
General safety requirements for UPS
EN62040-1/IEC62040-1/AS62040-1
EMC requirements for UPS
EN62040-2/IEC62040-2/AS62040-2 (Class C3)
Method of specifying the performance and test
requirements of UPS
EN62040-3/IEC62040-3/AS62040-3 (VFI SS 111)
The product standards in this table incorporate relevant compliance clauses with generic IEC and EN standards for
safety (IEC/EN/AS60950), electromagnetic emission and immunity (IEC/EN/AS61000 series) and construction
(IEC/EN/AS60146 series and 60529).
11.2
Environmental Characteristics
Table 11-2
Environmental characteristics
Item
Unit
Rated power (kVA)
80
100
120
160
200
Noise within 1m (in the
front)
dB (A)
61
65
Altitude
m
≤ 1500; derate power by 1% per 100m between 1500m and 3000m
Relative humidity
%RH
0 ~ 95%, non condensing
Operating temperature
°C
0 ~ 40°C
Storage and transportation
temperature for UPS
°C
Storage: -25°C ~ +55°C; transportation: -40°C ~ +70°C
Over-voltage level
Level 2
Pollution level
Level 2
Grid system
TN, TT, IT
11.3
Mechanical Characteristics
Table 11-3
Mechanical characteristics
Item
Unit
Rated power (kVA)
80
100
120
160
200
Dimensions
(D × W × H)
Packing excluded mm 1000 × 600 × 2000
Packing included
mm 1120 × 710 × 2215
Net weight
kg
385
430
430
475
520
Gross weight
Kg
435
480
480
525
570
Color
Black ZP7021
Protection degree, IEC (60529)
IP20 (front door open or closed)
Summary of Contents for EXM 0080kTK16FN01000