12.7 Electrical Characteristics (Bypass Input)
Item
U nit
Rated p ower (kV A )
250
Rated AC voltage
1
Vac
380/400/415, 3-phase 4-wire, sharing neutral with the rectifier input and providing neutral reference
to the output
Rated current
380 V
A
379
400 V
A
362
415 V
A
347
Frequency
2
Hz
50/60
Bypass voltage tolerance
%Vac
Upper limit: +10, +15 or +20, default: +15
Lower limit: -10, -20, -30 or -40, default: -20
Bypass frequency tolerance
%
±10 or ±20, default: ±10
T able 12.7 B ypass in pu t
N O T E:
1. F acto ry set to 38 0 V. 400 V o r 415 V can be selected by service en gin eer at site.
2. F acto ry set to 50 Hz. 60 Hz can be selected by service en gin eer at site.
12.8 Efficiency and Loss
Item
U nit
Rated p ower (kV A )
250
Rated normal mode loss (full load)
kW
10
Rated normal mode loss (empty load) kW
1
ECO mode loss (full load)
kW
2.5
Normal mode efficiency
Up to 96.8%
ECO mode efficiency
Up to 99.2%
Max. flow
m
3
/h
2550
T able 12.8 Efficien cy an d lo ss
12 Specifications
179
Vertiv™ Liebert® APM Plus User Manual
Summary of Contents for APM 0250kMK16FN02000
Page 1: ...Vertiv Liebert APM Plus User Manual 50 250 kVA UPS...
Page 8: ...vi This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Page 30: ...2 Overview 22 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Page 97: ...5 Operator Control and Display Panel 89 Vertiv Liebert APM Plus User Manual...
Page 188: ...12 Specifications 180 This page intentionally left blank Vertiv Liebert APM Plus User Manual...