ALPHA 900 - 1800
Battery charger / DC Power Supply

©2017 Vertiv Co. All rights reserved     |     ALPHA 900 - 1800     |     6012559     |     User Manual     |     v03     |     05.17

INSTALLATION 

 

 

 

CONNECTION 

 

 

 

ALPHA 1800 

 

ALPHA 900

 

IMPERATIVE VERTICAL INSTALLATION 

Connectors in bottom 

 

Option

 Kit  

6 007 983 

Side mounting

 

Ventilation : 

50mm free

 

space

 around 

ALPHA UNIT 

Front layout 

Front layout 

Side  
layout 

Side layout 

Bat : Battery

 

 

 Out : Load

 

 

External controls  

       4 : +Vcc 

   5 : 0V 
   6 : U setting (switch 2 set to external setting) 
   7 : IB setting (switch 3 set to external setting) 

   8 - 9 : ON / OFF static stop

 

(open = stop)

 

 10-11 : boost

 

Fault report

 

1-2

 : NO 

2-3

 : NC (closed at fault) 

Earth (



Mains  

(male IEC type) 

Fault 
fault 

Stop  Boost 

DJS 

curve

 C : 

  6A  

Alpha   900

 

16A  

Alpha 1800

 

220/240Vac 

50/60Hz 

Te/- wire 
    Mini      0.75mm² 
  900  MAXI 10mm² 
1800  MAXI 16mm² 

Terminal 1 to 11 

0,8mm²   mini 
2,5mm²  maxi

 

 

U & IB = 

option

 Kit  

External Potentiometer 

Réf. : 

6 002 928 

To 

more 

information, 

to 

see 

“6007539  Alpha  900  user’s  manual” 
or  “6008595  Alpha  1800  user’s 
manual 

 