Vertiv™ NetSure™ A50B50 DC Power Retrofit Installation and User Instructions
12
Figure 3.6
Connecting an Optional SM-Temp Module
Connecting the SM-TEMP Module’s CAN Terminals to the NCU CAN Bus
Note: Cable P/N 562868 is ordered
separately. A standard CAT5 cable
can be used provided the
terminations are aligned correctly.
J3 Pin 1 on CAN interface board is
connected to CAN-L input pin on
SM-TEMP. J3 Pin 2 on CAN
interface board is connected to
CAN-H input pin on SM-TEMP.
RJ-45
ANALOG
CAN
Orange
TB1
White-Orange
Cable P/N 562868
Cable P/N 562868
White-Orange: CAN L Terminal.
Orange: CAN H Terminal.
SM-TEMP Module
J3
(RJ-45)
CAN Interface Board
A50IFRM
A50EFRM
A50EFRM
Last Retrofit Frame in
NCU CAN Bus (see a
previous illustration for
multiple shelf
arrangement)
CAN Port (RJ-45) Located
on CAN Interface Board