NetSure
™
RDB Series
Installation and User Manual, Section 6041
Spec. No: 547692, 547693, 547499, 547694, 547695, 547615,
Document Code: Section 6041
547696, 547697, 547503, 547500, 547698, 547699, 547501
Revision K, April 28, 2017
[5]
Specifications and Technical Data
Conformity and Standards
The NetSure RDB Rack PDU (Power Distribution Unit) has the following agency approval ratings:
•
UL 60 950-1 + UL 1801 - Recognized (cURus)
•
In accordance with the Low Voltage Directive, 2006/95/EEC and including amendments by the CE Marking Directive,
93/68/EEC.
Environmental Characteristics
The NetSure RDB Rack PDU (Power Distribution Unit) is designed to operate under the following environmental conditions without
damage or degradation in electrical operating characteristics:
Operating Temperature
-40°F to +104°F (-40°C to +40°C) (Models L6 and L15).
-40°F to +113°F (-40°C to +45°C) (Models H2, H3, and M6).
Storage Temperature
-40°F to +176°F (-40°C to +80°C).
Relative Humidity
0 to 95%, non-condensing.
Operating Elevation
6562 ft (2000m) at full power.
Specifications
Model
Part
Number
Number
of
Outlets
Power Rating per Outlet
Power Rating per PDU
Input/Output
Voltage
(nominal)
RDB - Basic Rack PDUs
Max Watts
Max Amps
1
Max kW
Max Amps
1
L6
547692
6
420
10
2.5
60
-48Vdc
547693
630
15
3.8
90
547499
840
20
5.0
120
L15
547694
15
420
10
6.3
150
547695
630
15
8.4
2
200
2
547615
840
20
8.4
2
200
2
M6
547696
6
1050
25
6.3
150
547697
1260
30
7.6
180
547503
1470
35
8.4
2
200
2
H2
547500
2
3360
80
6.7
160
H3
547698
3
2100
50
6.3
150
547699
2520
60
7.6
180
547501
2940
70
8.4
2
200
2
1
Max Amps rated at end of battery discharge (42V).
2
PDU power rating limited to 200A, 8.4kW each.