Vertiv™ NetSure™ IPE Series -48 VDC Outdoor Rectifier Installation and User Manual
Proprietary and Confidential © 2022 Vertiv Group Corp.
6
WARNING!
The module is rated for continuous operation at full output power up to +55 °C (+131 °F). Operation
b55 °C (+131 °F) and +75 °C (+167 °F) will result in output power decrease. Operation above +75 °C (+167 °F) is
considered abnormal and should be used on a temporary
1
basis only.
1
Temporary Operation at Abnormal Temperature: Temporary operation is defined as a period of not more than
eight consecutive hours per day, and a total of not more than 15 days in a year, at a temperature above +75 °C
(+167 °F). (This refers to a total of 120 hours in any given year, but no more than 15 occurrences in that one-year
period.)
Other power rating values are as follows (refer to Figure 1.3):
a)
At an ambient temperature of +55 °C (+131 °F), the power delivered by the rectifier is 2000 W.
b)
At an ambient temperature b55 °C (+131 °F) and +75 °C (+167 °F) is power linear derating.
c)
At an ambient temperature of +75 °C (+167 °F), the power delivered by the rectifier is 0 W.
Figure 1.1 Output Voltage vs. Output Current
Figure 1.2 Power Derating Based on Input Voltage
0
10
20
30
40
50
60
0
5
10
15
20
25
30
35
40
45
O
utp
ut
V
ol
ta
ge
(
V
)
Output Current (A
)
Output voltage v.s. Output current at max. Power
0.0%
20.0%
40.0%
60.0%
80.0%
100.0%
120.0%
0
50
100
150
200
250
300
350
%
o
f o
utpu
t
po
w
er
Input voltage (Vac)
Output power vs. Input voltage and Vo>48V at Temp≤55
℃
85
176