Vertex SignalTrans IST-P Installation And Operation Manual Download Page 1

Programmable

Isolated 3 wire Potentiometer Transmitter

Model IST-P

Installation and Operation  Guide

i

SignalTrans® IST-P is a 2-wire loop-powered isolated potentiometer 

transmitter. It converts 3 wire potentiometer into a scalable linear 4~20mA 
output current. Microprocessor based designed make it flexible to accept up 
to 15 user defined linearization points. various input signals  including mV, V, 
mA, PT100 and 9 different thermocouples. The measuring unit and range are 
also configurable with a user-friendly software 

i

SignalWin® via PC.

Features

 

  Up to 15 User defined linearization points available

    The user linearization feature allows the volume of a tank’s contents to be 
    caculated from the height of the material in the container. Up to 15 
    linearization points can be defined by user in the measurement range.

■ 

Configurable without power connected

■ 

3750 Vrms isolation between input and output

■ 

2-wire loop-power technology 4 to 20mA analogue output

■ 

Fault signal on sensor break presettable

 Accept 200~60K ohms 3 wire potentiometer input

Specification

 

Input signal : 

3 wire 200~60K ohms potentiometer.

Measuring accuracy : 

±0.1%

A/D resolution : 

16 bits

Input sampling rate : 

<200mS.

Output signal : 

Analogue 4 to 20mA, 20 to 4mA.

Output resolution : 

0.6uA (15 bits)

Output response time : 

<200mS.

Load :

 Max. (VPower supply - 10 V) / 0.020 

Power supply : 

10 to 36 V, internal protection against polarity inversion.

Common mode rejection ratio : 

>80dB.

Galvanic isolation : 

3.75 KVrms. between input and output

Input current required 

≤3.8mA

Current limit 

≤23mA

Operating temperature : 

0to 55°C

Humidity : 

0 to 90% RH

Figure 1.  Dimension in mm

Installation

Mounting

Electrical Connection

Accessary

 

URC-1020 Interface cable

EzPro hand held programmer

                                  

Figure 2. Terminal connections

Wiring Specification : 

Srew tightening torque : 3.5 lb-in 
Wire range : 16~26 AWG
Wire strip length : 5~6mm

 

Wiring Precaution : 

1. Always keep signal wires away from power or contactor wires.
2. The power supply of 

i

SignalTrans® should not be shared with contactors, 

electrical motor and other inductive devices.

Operation

  
The output current are calibrated within the specified accuracy at factory. 
However, a recalibration is implemented to provide fine adjustments to the 
input and output signal in the field. This is accomplished by 

i

SignalWin® 

software. 

Configuration

 
The 

i

SignalTrans® transmitter is user configurable with the 

i

SignalWin® PC 

software and URC-1020 interface cable or a EzPro hand held programmer.

 

i

SignalWin® is user-friendly software. The lastest release version can be 

download free from 

www.vertex-tw.com

 

URC-1020 Interface cable

 consist of interface converter and USB plug. It 

can be purchased separately from 

i

SignalTrans® supplier.

During configuration the transmitter can work alone with or without connecting 
to a power source. The configuration connection is shown in Figure 3.

                                Figure 3. Configuration connection

Figure 4 show the configuration screen of 

i

SignalWin®. The help menu 

provides further detail information about the IST-P transmitter and the 
software. The Configurable parameters are :
1. 

Input signal : 

200~60K ohms

2. 

Measuring range : 

0.0~100.0 %

3. 

Output direction : 

Defines the scalable analogue output signal to be 4 to 

20mA or 20 to 4mA.
4. 

Fault signal on sensor break : 

Defines the output signal to be upscale 

(>20mA) or downscale (<4mA) on sensor break.
5. 

Offset Correction : 

Allows to eliminate the offset error of measuring value.

6. 

4~20mA Output Signal Adjustment : 

Zero and Span adjustment of output 

signal. A power source shoule be connected as Figure 5.
7. 

User defined linearization : 

Depend on the model No.. up to 15 user 

defined linearization points available
8. 

Measuring value : 

Read the measuring value from transmitter continually.

9. 

Device information : 

Indicate the device model, firmware version, series 

number and communication status.

Figure 4. Configuration screen

Figure 5. Output Signal Adjustment connection

Electromagnetic compatibility (EMC) : 

En 50081-2, En 50082-2

Dimension : 

shown in Figure 1.

Housing material : 

ABS plastic. UL 94V0

Weight : 

19g

Reviews: