background image

Model: WDV500, WDV600

WDV Wideview

Direct Vent Gas Fireplace

Installation and Operating Instructions

78D0011  3/13  Rev. 12

 

IF the InFOrMatIOn In these InstructIOns 

are  nOt  FOllOWeD  exactly,  a  FIre 

Or  explOsIOn  May  result  causInG 

prOperty DaMaGe, persOnal Injury Or 

lOss OF lIFe.

–  Do  not  store  or  use  gasoline  or  other 

flammable vapors and liquids in the vicinity 

of this or any other appliance.

–  What tO DO IF yOu sMell Gas

  •  Do not try to light any appliance.

  •  Do not touch any electrical switch; do not 

use any phone in your building.

  •  Immediately call your gas supplier from 

a  neighbor's  phone.  Follow  the  gas 

supplier's instructions.

  •  If you cannot reach your gas supplier, call 

the fire department.

–  Installation and service must be performed 

by a qualified installer, service agency or 

the gas supplier.

WarnInG: Improper installation, adjustment, 

alteration, services or maintenance can cause 

injury or property damage. refer to this manual. 

For  assistance  or  additional  information 

consult a qualified installer, service agency or 

the gas supplier.   

this appliance may be installed in an aftermarket*, 

permanently  located,  manufactured  home  (usa 

only) or mobile home, where not prohibited by local 

codes.
this appliance is only for use with the type(s) of 

gas indicated on the rating plate unless a certified 

kit is used.

*aftermarket: completion of sale, not for purpose of resale, form 

the manufacturer.

WarnInGs

Installer: leave this manual with the appliance.

cOnsuMer: retain this manual for future refer-

ence.

WarnInG

Due tO hIGh teMperatures, the applIance 

shOulD Be lOcateD Out OF traFFIc anD 

aWay FrOM FurnIture anD DraperIes.
chIlDren anD aDults shOulD Be alerteD 

tO  the  haZarDs  OF  hIGh  surFace 

teMperature anD shOulD stay aWay tO 

aVOID Burns Or clOthInG IGnItIOn.
yOunG chIlDren shOulD Be superVIseD 

When they are In the saMe rOOM as the 

applIance.
clOthInG Or Other FlaMMaBle MaterIal 

shOulD nOt Be placeD On Or near the 

applIance.
Keep  the  rOOM area  clear anD  Free 

FrOM cOMBustIBle MaterIals, GasOlIne, 

anD  Other  FlaMMaBle  VapOrs  anD 

lIquIDs.

780012
DVW/WDV cover

Summary of Contents for WDV500NTSC

Page 1: ...manual For assistance or additional information consult a qualified installer service agency or the gas supplier This appliance may be installed in an aftermarket permanently located manufactured home...

Page 2: ...Wiring 25 Command Center Wall Installation 25 Wall Switch Installation 25 SCS Wiring Diagram 26 Thank you and congratulations on your purchase of a Vermont Castings Group Fireplace PLEASE READ THE INS...

Page 3: ...by a qualified service person with glass door properly seated and sealed combustion leakage can occur CARBON MONOXIDE POISONING Early signs of carbon monoxide poisoning are similar to the flu with he...

Page 4: ...l combustion air from outside of the dwelling through the vent pipe These appliances have been tested by CSA and found to comply with the established standards for VENTED GAS FIREPLACES in the USA and...

Page 5: ...tents for shipping damage and immediately inform your dealer if any damage is found Do not install any unit with damaged incomplete or substitute parts Check your packing list to verify that all liste...

Page 6: ...8 0 m m 57 6 1470 mm 4 1 1 0 4 1 m m 57 6 1470 mm 35 6 905 mm Rough Opening Height 780012 DVW WDV dims 4656 1172 mm 8 6QE 211 mm Required Noncombustible Material Area Total Fireplace Width 343 6 O 707...

Page 7: ...These units can be installed in a bedroom Refer to the National Fuel Gas Code ANSI Z233 1 NFPA 54 cur rent edition the Uniform Mechanical Code current edition and Local Building Codes for specific ins...

Page 8: ...tion Failure to follow instructions exactly can create a fire hazard Theappliancecannotbeinstalledonacarpet tile or other combustible material other than wood flooring If installed on carpet or vinyl...

Page 9: ...rick tile slate steel or other materials with a UL fire rating of Zero may be used to cover the black painted face of the appliance It is permissible to bring combustible wall board to the top of the...

Page 10: ...ttempting installation Failure to do so could result in serious injury property damage or loss of life Operation of improperly installed and maintained venting system could result in serious injury pr...

Page 11: ...uld insulate the chase as you would the outside walls of your home This is especially important in cold climates Insulation should be considered a combustible material Maintain proper clearances to al...

Page 12: ...he meter regulator assembly 5 m above the meter regulator assy I Clearance to service regulator vent outlet 3 91 cm 3 91 cm J Clearance to nonmechanical air supply inlet 6 15 cm for appliances 10 000...

Page 13: ...f the pipe on the fireplace Vertical Dimension From the Floor of Unit to the Center of the Horizontal Vent Pipe Dimensions in Feet 50 From Floor to Center Outside Corner Inside Corner Termination Clea...

Page 14: ...ition Measure the vertical height X required from the base of the flue collars to the center of the wall opening Figure 12 Step 4 Using appropriate length of pipe section s attach to fire place with t...

Page 15: ...ired before a 90 elbow If a 90 elbow is fitted directly after 12 vertical section mounted to the top of the fireplace the maximum horizontal vent run before the termination or a vertical rise is 36 91...

Page 16: ...ough the wall 2 Remove soil to a depth of approximately 16 below base of snorkel Install drain pipe Install window well not supplied Refill hole with 12 of coarse gravel leaving a clearance of approxi...

Page 17: ...3 4 FP1179 max bends Figure 21 Maximum Elbow Usage FP1179 Up to two 45 elbows may be used within the horizontal run For each 45 elbow used on the horizontal plane the maximum horizontal length must be...

Page 18: ...g to the position of the flue exit Mark the center point where the vent will penetrate the ceiling Drill a small locating hole a this point Drop a plumb line from the inside of the roof to the ceiling...

Page 19: ...ible materials 6 Continue to add pipe sections until the height of the vent cap meets the minimum building code requirements NOTE You must increase vent height for steep roof pitches Nearby trees adjo...

Page 20: ...nt 4 Slide the inner vent onto the adapter collar for a minimum 1C v overlap 5 Locate the clamp at approximately 3 4 from the flex end and tighten 6 Secure the clamped inner section with three self ta...

Page 21: ...ribed by the flexible vent manufacturer and in such a way as to maintain concentric inner and outer vent spacing D Attaching flexible venting to vertical termination assemblies 1 When using Duravent p...

Page 22: ...sleet When using copper of flex connectors use only fittings approved for gas connections The gas control inlet is 3 8 NPT The gas control is equipped with a captured screw type pressure test point t...

Page 23: ...s WARNING Only persons licensed to work with gas piping may make the necessary gas connections to this appliance CAUTION A manual shutoff valve must be installed upstream of the appliance Union tee an...

Page 24: ...ectrical Wiring General 1 This fireplace is equipped with the Signature Control valve which operates on 6 volts The A C module plugs into the fireplace junction box A C power supply Four 4 AA batterie...

Page 25: ...t extend beyond the 15 ft wire cable provided If a longer distance is required the 15 ft may be extended up to 30 ft maximum by using two 2 SCSWEK cables plugged together Route the wire from junction...

Page 26: ...Command Center Optional Wall Switch Plug in Connector Stepper Motor to Control Board DC Power Green Ground Plug in Connector Control Board to Solenoid Gas In Gas Out Pilot Gas Tubing Valve Light 300 W...

Page 27: ...ectly WARNING Electrical connections should only be performed by a qualified licensed electrician Main power supply must be turned off before connecting the fan to the main electrical power supply or...

Page 28: ...ove the front floor screen frame by unfastening the four 4 screws securing the front and sides 2 Install the six 6 halogen light bulbs provided Do not touch light bulbs directly with fingers 3 Replace...

Page 29: ...ent Firebox Perimeter Burner Surface Rear Vent FP2434 Example of Stone Placement FP2702 rock and stone place GLASS ONLY PLACEMENT NOTE Two 2 bags of glass are supplied with the 500 Series fireplaces B...

Page 30: ...phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department C Use only your finger to push in the master switch Never use tools If the switch will not f...

Page 31: ...as go to next step 4 Press the master switch to the ON position Within eight 8 seconds it will beep once This indicates the system is ready 5 Press ON button Sparker will spark and pilot flame will li...

Page 32: ...LCD Backlight X Security Codes 16 X Countdown 6 hr Timer X Standard Thermostatic Control Mode X Smart Mode Thermostat Auto Flame Blower Modulation X Three Brightness Settings for Lights X Three Speed...

Page 33: ...s when the master switch Shutoff on the main burner is off RF Remote Receiver Push the RF receiver On Off button on the control board RF OFF On Off Beep once for ON and beep twice for OFF Learn Remote...

Page 34: ...ashes every 1 sec for 10 sec AC Power On GREEN solid Pressure Switch Failed Power Vent only One RED every 2 sec until manual reset Self Diagnostics Chart The Command Center has a self diagnostic LED e...

Page 35: ...an extended period of time Never leave anything on top of the surface of the transmitter FP2646 TSFSC display Information Bar Touch Area Logo Bar Menus Adjustment Controls Function Areas of the LCD Di...

Page 36: ...e Command Cen ter will flash for 10 seconds WARNING Do not use two 2 or more remote control sys tems in the same area with the same privacy code setting as they will communicate with each other This m...

Page 37: ...t Timer Mode a Push and hold the TIMER button for 3 seconds Or b Use the OFF down buttons to decrease the Set Time to zero Or c Slide down on the arrow buttons to exit TIMER mode and shut off the fire...

Page 38: ...ll remember this setting and the blower is still off see blower On Delay and Off Delay in the next section 4 After the signal is sent the ON up and OFF down but tons become flame height controller aga...

Page 39: ...the light button is flashing slide up and down on the arrow buttons will turn the light brightness to HIGH or Off directly without pressing the light button again to confirm AUX Control Optional The...

Page 40: ...tteries 3 LCD display shows funny display 3 Reset the transmitter see Resetting the Transmitter section 4 Appliance does not come on 2 The transmitter did not match 1 Make sure the transmitter has wit...

Page 41: ...year Make sure the burner porting pilot air opening and burner air opening are free of obstructions at all times Pilot Flame The flames from the pilot should be visually checked as soon as the heater...

Page 42: ...ement glass door assemblies MUST be supplied by the fireplace manufacturer No substitute materi als may be used Handle glass door with care to avoid striking or scratch ing it on hard objects To clean...

Page 43: ...Battery polarity wrong LED on the Command Center does not show solid green The 5 pin connector on the AC board broken or bent AC plug is plugged to AC mains Battery voltage low Using battery Check va...

Page 44: ...t 6 73D4521K 73D4521K 3 Glass Frame Assembly 1 78D0027K 78D1038K 4 Junction Box Assembly not shown 1 26D2128 26D2128 5 Panel Access Door 1 78D0040K 78D1046K Accessories Field Installed Options 6 Porce...

Page 45: ...78D0011 45 WDV Series Gas Fireplace REPLACEMENT PARTS SIGNATURE COMMAND SYSTEM 780012 DVW SG parts 6 09 1 2 3 4 15 5 6 7 8a 9 14 8b 8c...

Page 46: ...9D0030 7 Injector 2 59D0062 69D0226 58D0051 20H3156 8a Burner Assembly 1 78D0033 78D0033 8b Burner Assembly 1 78D1058K 78D1058K 8c Burner Assembly 1 78D1057K 78D1057K 9 Venturi 2 69D1026 69D1026 69D10...

Page 47: ...ones REPLACEMENT PARTS Item Description 500 Qty 600 Qty Part No 1 White Stone 1 5 5 78D0122 2 Light Gray Stone 2 5 5 78D0123 3 Dark Gray Stone 3 5 10 78D0124 4 Brown Stone 4 5 5 78D0125 5 Sand Stone 5...

Page 48: ...48 78D0011 WDV Series Gas Fireplace HOT 1 2 3 4 5 6 9 7 8 10 730024 KHLDV vent parts VENT components REPLACEMENT PARTS...

Page 49: ...4 9 Pipe Length 58DVA 09 1207 5DT 09 3 4 12 Pipe Length 58DVA 12 1206 5DT 12 5D12 3 4 24 Pipe Length 58DVA 24 1204 5DT 24 5D24 3 4 36 Pipe Length 58DVA 36 1203 5DT 36 5D36 3 4 48 Pipe Length 58DVA 48...

Page 50: ...rdance with the above provisions shall comply with NFPA 720 and ANSI UL 2034 listed and IAS certified Signage A metal or plastic identification plate shall be permanently mounted to the exterior of th...

Page 51: ...ited Lifetime Warranty will also be void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance and does not extend to 1 firebox burner ass...

Page 52: ...Ratings Model EnerGuide Ratings Fireplace Efficiency WDV500NTSC 64 4 WDV500PTSC 67 7 WDV600NTSC 70 2 WDV600PTSC 72 2 Vermont Castings Group 149 Cleveland Drive Paris Kentucky 40361 www vermontcasting...

Reviews: