9
Save These Instructions
Vermont Castings • Aspen 1920 Owner's Manual_R32 • 08/17
B. Clearances To Combustibles
Use the chart below together with the diagrams in Figure 4.3 to determine the required clearance for your particular installation.
Stove clearances are measured from the top plate to the combustible surface.
Chimney connector clearances are measured from the connector surface and take into account flue collar offset.
Unprotected Surfaces
Protected Surfaces
Stove Clearances
Stove Installed
Parallel to Wall
Stove in
Corner
Stove Installed
Parallel to Wall
Stove in
Corner
Side
Rear
Corners
Side
Rear
Corners
No Heat Shields
(A) 24"
(610 mm)
(B) 13"
(330 mm)
(C) 13"
(330 mm)
(D) 16"
(406 mm)
(E) 9"
(229 mm)
(F) 8"
(203 mm)
Top Exit, Rear Heat Shield
ONLY
(G) 24"
(610 mm)
(H) 11"
(179 mm)
(I) 13"
(330 mm)
(J) 16"
(406 mm)
(K) 9"
(229 mm)
(L) 8"
(203 mm)
Rear Exit, Rear Heat Shield
ONLY
(M) 24"
(610 mm)
(N) 11"
(179 mm)
N/A
(O) 16"
(406 mm)
(P) 9"
(229 mm)
N/A
Top Exit, Rear H.S., Single
Wall Connector Shields
1,2
(Q) 24"
(610 mm)
(R) 9"
(229 mm)
(S) 13"
(330 mm)
(T) 16"
(406 mm)
(U) 9"
(229 mm)
(V) 8"
(203 mm)
Top Exit, Rear H.S., Double-
Wall Connector Shields
1,3
(Q) 24"
(610 mm)
(R) 7"
(178 mm)
(S) 13"
(330 mm)
(T) 16"
(406 mm)
(U) 7"
(178 mm)
(V) 8"
(203 mm)
Chimney Connector
Unprotected Surface / Vertical
Protected Surface / Vertical
No Heat Shield
15" (381 mm)
11" (279 mm)
Using Heat Shields
2
13" (330 mm)
6" (152 mm)
Double-wall connector
3
6" (152 mm)
6" (152 mm)
Unprotected Surface / Horizontal
Protected Surface / Horizontal
Single Wall Connector
18" (457 mm)
11" (279 mm)
Double Wall Connector
6" (152 mm)
6" (152 mm)
Front Clearance to Combustibles
All Installations:
48" (1219 mm)
** A distance of 48" must be maintained between the stove and movable combustible items such as drying clothes, furniture, fire
-
wood, etc.
1
When a rear heat shield is installed on a top exit stove, the shield insert must be attached to the shield so the area behind the flue
collar on the stove is protected.
2
Chimney connector heat shields must extend exactly 24" (610 mm) above the top of the stove. No shielding can be used on the
connector above 24" (610 mm). The unshielded chimney connector above the 24" (610 mm) point must be 13" (330 mm) from an
unprotected wall.
3
In top exit installations, this clearance requires the use of the rear stove heat shield with the flue collar cover plate installed.
Figure 4.2