18
Save These Instructions
Vermont Castings • Aspen 1920 Owner's Manual_R32 • 08/17
Figure 5.4
- If the clearance between the chimney connector and
either the ceiling or the mantel is inadequate, a protective heat
shield is required.
ST244
Plymouth
fplc over mantel
12/99
* Note clearance
requirement
In Section 4 -
Clearance to
Combutsibles
Mantel
Chimney Connector
Heat Shield
*
*
Figure 5.5
- Special adapter kits are available from your local dealer
to simplify fireplace installations.
ST245
fireplace
flex connector
12/99
* Maintain required clearance.
See Section 4 - Clearance to
Combutsibles
16”US
18” (460 mm)Canada
Flex Connector
Fireplace
Adapter w/
Clean-out Tee
Min. 15”
(381mm)
*
*
Figure 5.6
- Masonry Wall Pass-through with single wall chimney
connector.
ST272
masonry wall pass through
w/ single wall
connector
12/99
Min. 2” (51mm) Chimney clear
-
ance to brick and combustibles
A
= Minimum 12” (305 mm) brick
construction between liner and
combustible framing materials
Min. 12”
(305 mm)
Fire clay
liner
A
A
Chimney Flue
Fire clay liner
Masonry
Chimney
constructed
to NFPA 211
Chimney
connector
U.S. Requirements:
The National Fire Protection Association (NFPA) has
established guidelines for use in the United States for passing
chimney connectors through combustible walls. Many
building code inspectors follow these guidelines.
Figure 5.6 shows one NFPA-approved method. All
combustible material in the wall is cut away to provide 12”
(305 mm) clearance to the connector. Brick and mortar are
used to enclose the clearance area.
Connection Through the Fireplace:
If your fireplace opening height is at least 21-1/2" (546 mm),
you may install a stove through the opening using a “positive
connection” kit available from your local dealer. These kits
provide a secure connection between the stove flue collar
and the chimney flue.
Confirm that the stove location is within the required clearance
specifications for the mantel and surrounding fireplace trim.
Refer to Section 4 - Wall Shields.
Floor protection requirements also apply to fireplace
installations. Refer to Section 4 - Floor Protection.
Wall Pass-throughs:
Whenever possible, design the installation so that the
connector does not pass through a combustible wall. If you
must include a wall pass-through in your installation, check
with your building inspector before you begin. Also check
with the chimney connector manufacturer for any specific
requirements.
Consult with your dealer regarding special connection
components available for use as wall pass-throughs. Use
only parts that have been tested and listed for use as a wall
pass-through.